8.5.

Powerful Mode Operation

• Purpose of this operation is to obtain the setting temperature quickly.
• When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
• Vertical Airflow Direction:-
- In "Manual" setting, the vane will automatically shift down 10° lower than previous setting.
- In "Auto" setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
• Powerful Mode will operate for 15 minutes only, after that it will shift back to previous operation mode.
• Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode button is changed.
8.6.

Economy Mode Operation

• Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
• When the Economy Mode is set, the set temperature will be automatically increased 0.5°C against the preset setting
temperature (Higher temperature: 30°C).
• This operation automatically will be running under Lo- Fan Speed.
• Vertical Airflow Direction:-
In "Manual" or "Auto" setting, the vane will automatically change to Auto Air Swing.
• Economy Mode will stop if:-
- Economy Mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Powerful mode button is pressed.
- Auto or Manual air swing button is pressed.
- Fan Speed control button is pressed.
- Quiet Mode button is pressed ON.
- Operation Mode is changed.
8.7.

Random Auto Restart Control

• If there is a power failure during air conditioner operation, operation will be automatically restarted after 3 to 4 minutes when the
power is resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)