Air Circulation Mode Operation; Automatic Mode Operation - Panasonic CS-C9CKPG Service Manual

Room air conditioner
Hide thumbs Also See for CS-C9CKPG:
Table of Contents

Advertisement

CS-C9CKPG CU-C9CKP6G / CS-C12CKPG CU-C12CKP6G
8.3.

Air Circulation Mode Operation

• When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences at low
airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
Air Circulation Mode Operation Time Diagram
8.4.

Automatic Mode Operation

Standard for Determining Operation Mode
• Indoor fan operates at SLo fan speed for 20 seconds.
• After judging indoor air temperature, the operation mode is determined and operation continued at the mode determined.
• After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation includes
Cooling mode operation.
• Room temperature adjustment.
The following are added to the setting temperature specified as above.
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.
20