Default Parameters - York DPC-1 Technical Information

Programmable digital thermostat with communication
Table of Contents

Advertisement

Micro-switch SW1 allow the configuration of the following pa-
rameters:
- Pin 1: Lock keyboard. In OFF the keyboard is not locked. In
ON the keyboard is locked and the locked keyboard icon
(key) is displayed. The keys that remain active are:
and
(Consult outdoor temperature).
- Pin 2: AUTO PROG mode activated. Defines whether the
automatic air condition mode with time schedule program-
ming (time schedule profiles) can be activated. OFF indi-
cates the AUTO PROG mode is deactivated, and ON indi-
cates the AUTO PROG mode can be selected.
- Pin 3: O/B signal: Set to OFF, heat is generated when the
O/B (24 VAC) signal is active, and cool when inactive. Set
to ON, cool is generated when the O/B (24 VAC) signal is
active, and heat when inactive.
- Pin 4: 2 minutes/4 minutes. Defines the time between the
end of one phase and when it can be active again. OFF
indicates 2 minutes, and ON, 4 minutes.
- Pin 5: Multi-stage. Defines single-stage (one stage can be
activated only) or multi-stage (more than one can be acti-
vated). OFF indicates single-stage and ON, multi-stage. In
heat, if stage W exists, in single-stage Y1 and W are acti-
vated.
- Pin 6: Single-speed fan. Defines whether the fan can oper-
ate at one or three speeds. OFF indicates 3 speeds and
ON, 1 speed. In single-speed, the wind icons are not dis-
played.
By default, all micro-switches are set to OFF.

Default parameters

OFF Mode.
Day occupation.
Set points:
- Cool set point in Unoccupied mode 30° C.
- Cool set point in Night mode 27° C.
- Cool set point in Day mode 24° C.
- Heat set point in Day mode 21° C.
- Heat set point in Night mode 18° C.
- Heat set point in Unoccupied mode 15° C.
AUTO Fan, in automatic.
Origin of the temperature, internal probe.
Cancellation of the temperature probes offsets.
NORMAL temperature control.
Profiles programmed for each day of the week, P1.
Alarms
The alarm codes are displayed at the bottom left of the screen,
overlapping hour and minutes.
The alarm codes are as follows:
- 0-90, machine error codes.
- 91, temperature origin selected is invalid.
- 92, indoor temperature sensor not calibrated.
- 93, communication alarm.
- 94, Failure with terminal "AL" connected.
- 95-99, Digital probe not detected.
When an alarm is generated, the wrench icon is displayed. If
the error is machine or communication, this icon flashes; if
not it remains static.
Filters. If the dirty filters icon is displayed flashing, the filters
need to be changed.
Dead battery. The dead battery icon indicates the batteries
are dead, and these should be changed. System configura-
tion is not lost when changing the batteries. Only day and
time are lost.
,
Table of failures
Code
Compressor discharge temperature surpased or
11 / 21 / 31
short circuited probe
High Pressure switch, outdoor fan overload or com-
12 / 22 / 32
pressor motor protection module
Low Pressure switch
13 / 23 / 33
Indoor fan thermal switch
14
Repeated start-ups in cool, or suction temperature
15 / 25 / 35
< -25°C
Liquid temperature < -30°C
16
Gas 1 or electrical heater 1
41
42
Gas 2 or electrical heater 2
43
Electrical heater 3
Electrical heater 4
44
Economizer or hot water coil
45
Smoke detector, fire thermostat or air discharge tem-
46
perature probe (rooftop only) >80°C
Selected probe not valid or short circuited probe
91
Thermostat internal probe not calibrate
92
No communication between the thermostat and the main
93
PCB (Yklon)
94
Failure with terminal "AL" connected
95
Digital probe S5 not detected
96
Digital probe S6 not detected
Digital probe S7 not detected
97
Digital probe S8 not detected
98
99
Outdoor digital probe not detected
Temperature control
The purpose of this thermostat is to keep the room at the
temperature established by the set points. When operating in
AUTO or AUTO PROG, the heat and cool set points are used.
However, when operating in HEAT the heat set points are used
only, and when operating in COOL the cool set points are
used only. When the temperature between the real tempera-
ture and the set point is more than 0.2° C, the first stage Y1 is
activated. If after a while (depending upon the temperature
control operating mode TURBO, NORMAL, ECONOMY) the
temperature has not recovered, the second stage Y2 is acti-