Selection Of Outdoor Probe Type - York DPC-1 Technical Information

Programmable digital thermostat with communication
Table of Contents

Advertisement

- C-n: the thermostat is not in communication with the ma-
chine. The communication error Er 93 would not be displayed
on screen.
The active keys are:
-
Allow changing the selected mode.
-
Memorizes selected value, and goes back to the
user programming menu.
-
Cancels changes made, and goes back to user pro-
gramming menu.

Selection of outdoor probe type

Submenu P5
The clock digits display P5, indicating program 5.
The temperature digits display EA and Ed, which mean:
- EA. The thermostat displays the value of the analogue out-
door probe installed on the YKlon board or on the econo-
miser board.
- Ed. The thermostat displays the value of the digital outdoor
probe connected to the thermostat communications termi-
nal. Both microswitches of the digital probe must be se-
lected in ON position. In this case, the maximum number of
digital remote probes will be three.
The active keys are:
-
Allow changing the selected mode.
-
Memorizes selected value, and goes back to the
user programming menu.
-
Cancels changes made, and goes back to user pro-
gramming menu.
14
Micro-switches for configuration of the
thermostat
The SW1 micro-switches for configuration are inside the ther-
mostat, in the back of the front panel.
To open the thermostat correctly, please read the installation
instructions in this manual: Fastening the thermostat.
For standard thermostat operation, these pins are factory-set
to OFF. Nevertheless, these settings can be change in ac-
cordance to user needs. The functions of each one are as
follows.
DETAIL "A"
ON
1
2
3
4
MICRO-SWITCHES SW1
"A"
REAR OF
FRONT
PANEL
THERMOSTAT
BASE
5
6