START
Gas supply on
YES
Pilot lights with Piezo
YES
Pilot stays lit
YES
Pilot lights main
burner
YES
System OK
1414
Troubleshooting
Honeywell Valve (UVL-R series)
CHECK
• Supply line hooked up
NO
• Shutoff valve open
• Lockout has engaged. Wait 60 seconds
and try again
• Piezo screws are tight for good ground
• For spark at electrode while depressing
NO
piezo - 1/8" gap to pilot hood needed
• All wiring connections
• Replace piezo ignitor
• For air in the lines
• Thermopile needs a minimum of 325mV
• All wiring connections
NO
• Replace thermopile
• Thermocouple needs a minimum of 14mV
• Defective valve. turn to pilot, meter should
read greater than 100mV. If not, replace the
valve.
• Valve turned on
NO
• Wall switch is not turned on
• Thermopile needs a minimum of 325mV
• Plugged burner
UVL Series