7-2-2. Installation Place

• A place which provides the spaces around the indoor unit as shown in
the above diagram.
• A place where there is no obstacle near the air inlet and outlet.
• A place which allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the indoor unit comes to at
least 2m height.
Also it must be avoided to put anything on the top of the indoor unit.
CAUTION
• Direct sunlight to the indoor unit wireless receiver should be
avoided.
• The microprocessor in the indoor unit should not be too close to
r-f noise sources.
(For details, see the owner's manual.)
Remote controller
• A place where there are no obstacles such as a curtain that may block
the signal from the indoor unit.
• Do not install the remote control in a place exposed to direct sunlight
or close to a heating source, such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or
stereo equipment. (This is necessary to prevent image disturbances or
noise interference.)
• The location of the remote control should be determined as shown
below.
(Side view)
(Top view)
Indoor unit
Reception range
Remote
Reception
control
range
* : Axial distance
Fig. 7-2-1

7-2-3. Cutting a Hole and Mounting Installation Plate

Cutting a Hole
When install the refrigerant pipes from the rear.
The center of the pipe
hole is above the arrow.
Fig. 7-2-2
1. After determining the pipe hole position on the mounting plate (A)
drill the pipe hole (∅65 mm) at a slight downward slant to the outdoor
side.
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate,
be sure to use a pipe hole brim ring sold separately.
For installation of the indoor unit, use the paper pattern on the back.
1. Securely fit the installation plate onto the wall by screwing it in the
2. To mount the installation plate on a concrete wall with anchor bolts,
3. Install the installation plate horizontally in the wall.
Remote control
• In case of block, brick, concrete or similar type walls, make 5 mm dia.
Pipe
• Insert clip anchors for appropriate 7 mounting screws.
hole
∅65 mm
• Install the installation plate using 4 to 6 pieces of mounting screw
100 mm

7-2-4. Electrical Work

1. The supply voltage must be the same as the rated voltage of the air
2. Prepare the power source for exclusive use with the air conditioner.
• Wire type : More than H07RN-F or 245IEC66 (1.0 mm
– 28 –

Mounting the Installation Plate

Anchor bolt holes
Hook
170
85
Thread
Hook
Pipe hole
Weight
Indoor unit
Fig. 7-2-3
When the installation plate is directly mounted on the wall
upper and lower parts to hook up the indoor unit.
utilize the anchor bolt holes as illustrated in the above figure.
CAUTION
When installing the installation plate with a mounting screw, do not
use the anchor bolt hole. Otherwise the unit may fall down and result
in personal injury and property damage.
5 mm dia. hole
7 Mounting
Clip anchor
(local parts)
Fig. 7-2-4
CAUTION
Failure to firmly install the unit may result in personal injury and
property damage if the unit falls.
holes in the wall.
NOTE
securing four corners with screws.
conditioner.
NOTE
FILE NO. SVM-05019
62
82.5
1
Installation
Hook
plate
Pipe hole
7
Mounting screw
Anchor bolt
Projection
15 mm or less
screw
∅4 x 25 s
2
or more)

Hide quick links: