Preparing The Boiler For Operation - Buderus 800 - 24 User Manual

Gas wall hung boiler condensing
Table of Contents

Advertisement

Users manual
6
Commissioning
6.1

Preparing the boiler for operation

Note the operating instructions of the control unit.
Open the control panel cover.
Check the water pressure (fig. 1, item 3).
If the pressure is below 1.0 bar, top up water and
purge air from the system.
Max. water pressure 2.0 bar.
If water is lost frequently, have a specialist company
look for and eliminate the cause.
Adjust the flow temperature on the controller
(fig. 1, item 1) using table 1.
Adjust the hot water temperature on the controller
(fig. 1, item 2) using table 2.
Use the control unit or remote control unit to set
the room temperature to maximum.
Open the gas service valve: push in and turn to the
left in vertical position (fig. 1, item 4).
Turn the mains switch (fig. 1, item 5) into position "I".
The boiler runs through the start-up program and the
burner is ignited after approx. 30 seconds.
Close the control panel cover.
Use the control unit or remote control unit to adjust
the room temperature to the desired value.
Control unit
Digital Room Controller
HW4201, RC
ON/OFF temperature controller, 24 V
Tab. 1
Flow water temperature
* Basic setting: the actual flow water temperature is determined by the digital control system.
Have specific system settings adjusted on the digital control system by the specialist heating system company.
Application
Minor convenience, small heat losses
Average convenience, medium heat losses
Optimum convenience, normal heat losses
Tab. 2
Hot water temperature
Subject to modifications resulting from technical improvements !
4
Application
i
RT
Floor heating
Radiator heating
Floor heating
Radiator heating
Users manual Buderus 800 - 24/29/43/60 and 800 - 24T25/29T25 H/V • Edition 02/2006
5
I
0
1
1
3
Fig. 1
Control panel, pressure display, gas service valve
Controller position / flow temperature
1
(40
8
(80 °C, factory setting)*
1
(40
6
(40 °C, new building) up to
8
(80 °C, old building)
Controller
Hot water temperature of external reservoirs
position
1
5
10
11
KW
0
1
1
2
2
10
1
10
1
10
C)*
°
C)
°
27
C
°
40
C
°
60
C
°
Buderus Ltd. • http://www.buderus-domestic.co.uk
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

800 - 29800 - 43800 - 60800 - 24t25800 - 29t25 h800-24 ... Show all

Table of Contents