8.2.4 Separate a UPS unit from the Parallel System (System Redundancy)

One UPS unit of the Parallel System has to be turned Off, while the load is shared between the other
units supplying the parallel bus.
1.
Disconnect the inverter, only on this unit, by pressing "Inverter OFF" ( O ) key and hold until the
LED Inverter (7) turns OFF.
With redundant system, pressing the key OFF the inverter shuts down and it will stay OFF.
If by pressing the key "O" the load is transferred to the mains and the inverter remains operating, it means
the system is not redundant.
In this case is not possible to switch-OFF one unit without transferring the load on mains).
Load supplied from inverter(s) of the other Unit(s) of the Parallel System.
2.
Open the output switch Q1 only on this unit.
LED Alarms is lit and the LED Operation is Off.
3.
Perform the command "Total Off" only on this unit.
Perform the command "Total Off" by entering the screen (see
Section 7.5):
COMMANDS / REQUEST TOTAL OFF
4.
Remove the external battery fuses only on this unit.
In case of GE battery cabinet:
− Open fully and remove the cover of fuse-holder by using correctly the handle;
Remove the fuses from their place, re-install and close fully the cover of fuse-holder.
5.
In order to discharge the DC link capacitors, insert the inverter by pressing "Inverter ON" ( I ) key
only on this unit.
Remark:
Command INVERTER ON will be enabled only when the inverter
voltage of each phase decreases below 7 Vac (about 30 seconds).
Before proceeding to step 6, check on the display panel that the DC
link voltage (both polarities) Vp and Vn has reached the max.
voltage of 5 Vdc (about 30 seconds).
The acoustical alarm is activated, press "MUTE" key (from Home
screen) to reset it.
6.
Disconnect the inverter, only on this unit, by pressing "Inverter OFF" ( O ) key and hold until the
LED Inverter (7) turns OFF.
7.
Switch OFF the mains power, only on this unit, at the AC input distribution panel.
WARNING !
In case the unit should be disconnected and removed from the operating system,
the operation MUST BE PERFORMED BY QUALIFIED PERSONS.
If an intermediate unit must be disconnected from a Parallel System pay attention
do not open the control bus: keep the plugs J3 and J4 connected to the board "P16 -
Connector adapter RPA" (see Section 5.8.4).
For any further intervention contact nearest Service Centre.
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
END OF PROCEDURE
Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
Home\Meter
INVERTER
f
:
L1
:
L2
:
L3
:
T
:
SYNCHRONISED
Home\ Meter
BOOSTER
f
:
L1
:
L2
:
L3
:
Vp
:
Vn
:
Operating Manual LP 33 Series 60-80-100-120 kVA / S2
50.0 Hz
7 V
7 V
7 V
OK
50.0 Hz
397 V
395 V
393 V
5 V
5 V
Page 87/103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents