Place Of Installation - GE LP 33 Series Operating Manual

60 – 80 – 100 – 120 kva 400 vac ce / series 2
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

5.4

PLACE OF INSTALLATION

WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
The UPS should be installed in a restricted area where only qualified personnel should be admitted.
The place of installation should be clean, dust-free, and provided with proper ventilation or air-
conditioning.
Verify for sufficient floor load capacity (see Section 5.1.1).
We strongly advice that the ambient temperature should not exceed 20° ÷ 25°C / 68° ÷ 77°F (max. 35°C
/ 95°F). See Section 5.5.
Positioning of the UPS LP 33 Series 60 – 80 - 100 - 120 kVA
Min.
400mm / 16"
Min.
800mm / 32"
LP 33 Series 60 - 80 kVA
Fig. 5.4-1 Positioning LP 33 Series 60 – 80 - 100 - 120 kVA
The LP 33 Series UPS can radiate radio frequency energy.
Although some RFI (Radio Frequency Interference) filtering is inherent to the UPS there is no guarantee
that the UPS will not influence sensitive devices such as cameras and monitors that are positioned close
by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
NOTE !
Operating temperature is very important for valve regulated battery (maintenance
free).
Operation at temperatures higher than 20°C (68°F) will reduce life expectancy.
Respect the prescription VDE 0510, those of the battery supplier and other local
standards.
The installation and cabling of the battery must be performed by QUALIFIED
SERVICE PERSONNEL only.
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
Min.
400mm / 16"
Min.
800mm / 32"
LP 33 Series 100 - 120 kVA
The rear panel of the UPS may be mounted
flush to a wall or other structure.
Clearance around the front of the unit
should be sufficient to enable free passage
of personnel with the doors fully open, and
to allow sufficient airflow to the door vents.
To guarantee proper cooling air exhaust,
the recommended minimum clearance
between ceiling and top of the UPS is
400mm (16").
A single-phase power outlet (230 Vac)
should be provided near the UPS for
connection of power tools, test equipment
or connectivity devices.
This outlet must be grounded.
Operating Manual LP 33 Series 60-80-100-120 kVA / S2
Page 26/103