7.3.4 Separate a Unit from the parallel system (System Redundancy)
Initial status: Load supplied from all Inverters.
First operated unit
1. Press and hold "inverter off" ( O ) key on the Unit to separate, until the LED turns OFF.
Load supplied from Inverter(s) of the other Unit(s) of the parallel system
First operated unit
2. Open Q1 (Pos. O) and, only when the LED service check is ON, press "total off" button
on the Unit to separate.
•
Press mute, to reset alarm and buzzer.
First operated unit
Modifications reserved
OPM_SGS_USM_M40_M50_1US_V020.doc
All other units of the system
.
All other units of the system
All other units of the system
Operating Manual SG Series 400 & 500 kVA
►
Continue
Page 58/86