Troubleshooting
4.17 Position Sensor Abnormality
H6
Remote Control
Display
Method of
A compressor start-up failure is detected by checking the compressor running condition through
Malfunction
the position detection circuit.
Detection
If the error repeats 8 times, the system is shut down.
Malfunction
Reset condition: Continuous run for about 5 minutes without any other error
Decision
Conditions
Disconnection of the compressor relay cable
Supposed
Defective compressor
Causes
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage out of specification
78
SiENBE07-618_C
Service Diagnosis