Position Sensor Abnormality - Daikin SiENBE07-618_C Service Manual

C-series inverter pair duct connected type
Table of Contents

Advertisement

Troubleshooting

4.17 Position Sensor Abnormality

H6
Remote Control
Display
Method of
A compressor start-up failure is detected by checking the compressor running condition through
Malfunction
the position detection circuit.
Detection
„ If the error repeats 8 times, the system is shut down.
Malfunction
„ Reset condition: Continuous run for about 5 minutes without any other error
Decision
Conditions
„ Disconnection of the compressor relay cable
Supposed
„ Defective compressor
Causes
„ Defective outdoor unit PCB
„ Start-up failure caused by the closed stop valve
„ Input voltage out of specification
78
SiENBE07-618_C
Service Diagnosis