Inverter Powerful Operation - Daikin SiENBE07-618_C Service Manual

C-series inverter pair duct connected type
Table of Contents

Advertisement

Main Functions
1.9

Inverter POWERFUL Operation

Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Detail
When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Operation mode
COOL
DRY
HEAT
FAN
AUTO
Ex.) : POWERFUL operation in cooling mode.
Target temp.
26
Dry rotating speed + 50 rpm
Same as cooling / heating in
It should be the lower limit of
cooling temperature.
18°C
POWERFUL
ON
POWERFUL
OFF
Fan
50 rpm
H tap
Set tap
Fan speed
H tap + 50 rpm
H tap + 50 rpm
H tap + 50 rpm
POWERFUL operation
20 minutes
SiENBE07-618_C
Target temperature
18°C
Lowered by 2.5°C
30°C
The target temperature is kept
unchanged.
It counts 20 minutes. also in the
remote control.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.
Function and Control
(R7096)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents