Setting the boiler control function modes

It is possible to select the various boiler control function
modes by using the function selector knob A and the
D.h.w. temperature control knob B (Fig. 5).
The knob B is used just for boiler setting and doesn't
affect the boiler functions during the normal operation.
During the function modes setting, the boiler does not
operate.
E
A
B
Fig. 5
9.6

Reignition frequency setting

It is possible to select the minimum time that must pass
between two ignitions of the burner in c.h. function
mode.
1
Turn the boiler ON positioning the function selec-
tor knob A as indicated in Fig. 6.
E
B
Fig. 6
2
Keep pressed the reset button C for about 10 sec-
onds until the lock ---out signal lamp D blinks.
16
Boiler in stand --- by condition.
(function control in
position).
position)
Anti--- freeze system active.
Boiler ON condition
(function control in
or
position)
position)
Faulty boiler or irregular
operation as:
--- Empty primary circuit
--- No primary circuit flow
--- Lack of burner ignition
--- Lack of burner ignition
--- Excessive temperature in
the primary circuit.
--- Faulty temperature probe
--- Faulty air pressure switch
C
D
A
C
Fig. 7
3
The lamps E should give the indication as in Fig. 7
--- Fig. 8 (reignition frequency). If not, press the
reset button repeatedly to obtain it.
Fig. 8
At this step it is possible to visualize the current setting
by keeping the reset button C pressed for more than 5
seconds. The lamps E will flash a number of times
corresponding to the setting (Fig. 9).
4
To change the setting turn the knob B on a posi-
tion corresponding to the desidered delay.
By turning the knob B, the lock ---out signal lamp
D blinks quickly (2 per seconds) indicating that
the setting has changed and must be memo-
rised.
0
Fig. 9
5
To memorize the setting keep pressed the reset
button C for about 5 seconds until the lights E
briefly blinks simultaneously.
6
To reset the boiler to the normal operation turn it
OFF and ON by the function selector knob A. In
any case, the boiler automatically resets to its nor-
mal operation after 10 minutes.
Factory setting = 3minutes
9.7

Ignition gas pressure adjustment

1
Turn the boiler OFF.
2
Remove the front panel of the case.
D
3
Open the gas valve outlet pressure test point (8,
see section 10.2) and connect the gauge.
4
Turn the boiler ON positioning the function selec-
tor knob A as indicated in Fig. 10 and ensure that
ON
LD1
LD2
E
Where:
Lamp OFF
Lamp ON
2
3
1 ½
4
3
5
1
2
6
1
7
B
LD3
3 ½
4
Delay (minutes)
Setting No.