To Set Up The Initial And Verify Delay - Honeywell System 800 Operator's Manual

Gent fire alarm panel operator’s manual & log book
Hide thumbs Also See for System 800:
Table of Contents

Advertisement

To set up the Initial
and Verify delay
The
alarm sounders
The
Initial delay
(factory set to 30 seconds). This delay is imposed on the
alarm sounders at the beginning of a fire condition, providing the Delay
facility is active with the delay LED lit.
The
Day mode delay
This delay value can be up to 9 minutes 59 seconds. Note this value is
the total delay duration from the start of a fire condition. It is made active
on pressing the Verify button when initial Delay is active and delay
LED is lit.
P1
1
2
A2
3
min
Alarm delay operation
Initial delay
30s factory default
Day mode delay
Start of
Maximum alarm delay
alarm
[Initial delay]
A2
(initial Verify delay)
Select
Press to increment
0 to 9 minutes.
Next
Press to select
seconds field [ ]
Press to increment
from 0 to 59 seconds.
32
796689 (4188-658) i2_04/07
The delay mode facility (also called Day
mode) provides a delay before sounding
alarms in the event of a fire.
in the system can be delayed on a fire condition.
can be configured up to 9 minutes 59 seconds
is an extended alarm delay to verify a fire alarm.
9min 59sec
[Day mode delay]
A2
(extended Verify delay)
Select
Press to increment
0 to 9 minutes.
Next
Press to select
seconds field [ ]
Press to increment
from 0 to 59 seconds.
Previous
Next
Press to select field [ ]
P1
1
2
3