FR-A
700
Instruction Manual Supplement
For the FR-A740 and FR-A720, the following specifications are
added.
(1)
Acceleration/deceleration time switching frequency (Pr. 147 )
When output frequency reaches Pr. 147 Acceleration/deceleration time switching
frequency or higher, the acceleration/deceleration time automatically switches to
Pr. 44 Second acceleration/deceleration time and Pr. 45 Second deceleration time settings.
The RT signal is not necessary for switching the acceleration/deceleration time.
Pr.
Number
Acceleration/
deceleration time
147
switching
frequency
• When the RT signal (X9 signal) turns ON, the acceleration/deceleration time
switches to the second (third) acceleration/deceleration time even when the
output frequency has not reached the Pr. 147 setting. Priority of switching is
X9 signal > RT signal > Pr. 147 setting.
• If the Pr. 147 setting is lower than Pr. 10 DC injection brake operation frequency or
Pr. 13 Starting frequency setting, the acceleration/deceleration time switches to
the Pr. 44 (Pr. 45) setting when the output frequency exceeds the Pr. 10 or Pr. 13
setting.
Pr. 147 Setting
9999 (initial value)
0.00Hz
0.01Hz Pr. 147 Set
frequency
Set frequency Pr. 147
Series
Initial
Name
Value
9999
Deceleration Time
Output frequency Pr. 147
Pr. 147 Output frequency
Setting
Range
Frequency when automatically
0 to
switching to the acceleration/
400Hz
deceleration time of Pr. 44 and Pr. 45.
9999
No function
Acceleration/
Pr. 7, Pr. 8
Pr. 44, Pr. 45
: Pr. 7, Pr. 8
: Pr. 44, Pr. 45
Pr. 7, Pr. 8
1/4
Description
Description
No automatic switching of
the acceleration/
deceleration time
Second acceleration/
deceleration time from a
start
Acceleration/deceleration
time automatic switching
No automatic switching,
since output frequency will
not reach the switching
frequency