Mitsubishi Electric FR-A720-0.4K Instruction Manual page 125

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Parameter List
Parameter
RUN terminal
190
function selection
SU terminal
191
function selection
IPF terminal
192
function selection
OL terminal function
193
selection
FU terminal function
194
selection
ABC1 terminal
195
function selection
ABC2 terminal
196
function selection
118
Incre-
Initial
Name
ments
Value
1
0
1
1
1
2
1
3
1
4
1
99
1
9999
Range
Description
0, 100: Inverter running (RUN)
1, 101: Up to frequency (SU)
0 to 8,
2, 102: Instantaneous power failure/
10 to 20,
undervoltage (IPF)
25 to 28,
3, 103: Overload alarm (OL)
30 to 36, 39,
4, 104: Output frequency detection (FU)
41 to 47, 55,
5, 105: Second output frequency detection (FU2)
64, 70, 84,
6, 106: Third output frequency detection
85, 90 to 99,
(FU3)
100 to 108,
7, 107: Regenerative brake pre-alarm (RBP)
110 to 116,
8, 108: Electronic thermal O/L relay pre-
120,
alarm (THP)
125 to 128,
10, 110:PU operation mode (PU)
130 to 136,
11, 111: Inverter operation ready (RY)
139,
12, 112:Output current detection (Y12)
141 to 147,
13, 113:Zero current detection (Y13)
155, 164, 170,
14, 114:PID lower limit (FDN)
184, 185,
15, 115:PID upper limit (FUP)
190 to 199,
16, 116:PID forward/reverse rotation
9999
output (RL)
17, —: Electronic bypass MC1 (MC1)
18, —: Electronic bypass MC2 (MC2)
19, —: Electronic bypass MC3 (MC3)
20, 120:Brake opening request (BOF)
25, 125:Fan fault output (FAN)
26, 126:Heatsink overheat pre-alarm (FIN)
27, 127:Orientation complete (ORA)
28, 128:Orientation fault (ORM)
30, 130:Forward rotation output (Y30)
31, 131:Reverse rotation output (Y31)
32, 132:Regenerative status output (Y32)
33, 133:Operation ready 2 (RY2)
34, 134:Low speed output (LS)
35, 135:Torque detection (TU)
36, 136:In-position (Y36)
0 to 8,
39, 139:Start time tuning completion (Y39)
10 to 20,
41, 141:Speed detection (FB)
25 to 28,
42, 142:Second speed detection (FB2)
30 to 36, 39,
43, 143:Third speed detection (FB3)
41 to 47, 55,
44, 144:Inverter running 2 (RUN2)
64, 70, 84,
45, 145:Inverter running and start
command is ON (RUN3)
85, 90, 91,
46, 146:During deceleration at occurrence
94 to 99,
of power failure (retained until
100 to 108,
release) (Y46)
110 to 116,
47, 147:During PID control activated (PID)
120,
55, 155:Motor temperature detection (Y55)
125 to 128,
64, 164:During retry (Y64)
130 to 136,
70, 170:PID output interruption (SLEEP)
139,
84, 184:Preparation ready signal (RDY) *1
141 to 147,
85, 185:DC current feeding (Y85)
155, 164,
90, 190:Life alarm (Y90)
170, 184,
91, 191:Fault output 3 (power-off signal) (Y91)
185, 190,
92, 192:Energy saving average value
191, 194 to
updated timing (Y92)
199, 9999
93, 193:Current average monitor signal (Y93)
94, 194:Fault output 2 (ALM2)
95, 195:Maintenance timer signal (Y95)
96, 196:Remote output (REM)
97, 197:Alarm output 2 (ER)
98, 198:Alarm output (LF)
99, 199:Fault output (ALM)
9999: No function
0 to 99: Positive logic
100 to 199: Negative logic
*1
Available only when used with the FR-
A7AP/FR-A7AL.
Available
only
*2
mounted and SFV5RU
used.
: enabled
× : disabled
*1
*1
*1
*1
*1
*1
*2
when
FR-A7AZ