Mitsubishi Electric FR-A720-0.4K Instruction Manual page 201

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

FR-A740-
K
Rated fuse voltage(V)
Without power
Fuse
factor improving
maximum
reactor
allowable
With power
rating (A)*
factor improving
reactor
Molded case circuit
breaker (MCCB)
maximum allowable
rating (A)*
* Maximum allowable rating by US National Electrical Code.
Exact size must be chosen for each installation.
Class RK5 or Class T or Class L fuses or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
FR-A740-
K
Rated fuse voltage(V)
Without power
Fuse
factor improving
maximum
reactor
allowable
With power
rating (A)*
factor improving
reactor
Molded case circuit
breaker (MCCB)
maximum allowable
rating (A)*
* Maximum allowable rating by US National Electrical Code.
Exact size must be chosen for each installation.
(4) Wiring of the power supply and motor
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL Listed copper, stranded
wires (rated at 75°C) and round crimping terminals. Crimp the crimping terminals with the crimping tool recommended
by the terminal maker.
(5) Short circuit ratings
• 200V class
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 264V Maximum.
• 400V class
55K or lower
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 528V Maximum.
75K or higher
Suitable For Use in A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical Amperes, 550V Maximum.
194
0.4
0.75
1.5
2.2
6
10
15
20
6
10
10
15
15
15
15
15
75
90
110
132
300
350
400
500
350
450
500
600
3.7
5.5
7.5
11
480V or more
30
40
70
80
25
35
60
70
20
30
40
50
160
185
220
250
500V or more
600
700
800
900
800
800
1000 1200 1200 1200 1600 1600 2000 2000
15
18.5
22
30
90
110
150
175
90
100
125
150
70
90
100
125
280
315
355
400
1000 1100 1200 1350 1500 1800
37
45
55
200
250
300
175
200
250
150
200
250
450
500

Hide quick links: