Mitsubishi Electric FR-A720-0.4K Instruction Manual page 115

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Parameter List
Parameter
Reset selection/
disconnected PU
75
detection/PU stop
selection
Fault code output
76
selection
Parameter write
77
selection
Reverse rotation
78
prevention selection
Operation mode
79
selection
Communication
startup mode
340
selection
108
Incre-
Initial
Name
ments
Value
1
14
1
0
1
0
1
0
1
0
1
0
Range
Description
You can select the reset input acceptance,
disconnected PU (FR-DU07
PU04) connector detection function and PU
0 to 3,
stop function.
14 to 17
For the initial value, reset always enabled,
without disconnected PU detection, and
with PU stop function are set.
0
Without fault code output
1
With fault code output
2
Fault code output at fault occurrence only
0
Write is enabled only during a stop
1
Parameter write is disabled.
Parameter write is enabled in any
2
operation mode regardless of operating
status.
0
Both forward and reverse rotations allowed
1
Reverse rotation disallowed
2
Forward rotation disallowed
0
External/PU switchover mode
1
Fixed to PU operation mode
2
Fixed to External operation mode
3
External/PU combined operation mode 1
4
External/PU combined operation mode 2
6
Switchover mode
External operation mode (PU operation
7
interlock)
0
As set in Pr. 79.
Started in the Network operation mode.
When the setting is "2", it will resume the
1, 2
pre-instantaneous power failure operation
mode after an instantaneous power failure
occurs.
Started in the Network operation mode.
Operation mode can be changed between
the PU operation mode and Network
operation mode from the operation panel.
10, 12
When the setting is "12", it will resume the
pre-instantaneous power failure operation
mode after an instantaneous power failure
occurs.
: enabled
× : disabled
/FR-PU07
/FR-
×
*
×
*