Functional Development Specifications
Installation/Service Modes
● If your indoor machine does not support the setting mode, then you may not be able to edit the settings or apply your changes.
Main
Sub
menu
menu
Wireless remote controller Option
1
setting/checking (1)
Wireless remote controller Option
2
setting/checking (2)
1
Blade
3
setting/checking
ERV option
4
Setting/checking
5
Room Temperature compensation
6
Number of connected units
7
0
1
2
2
1
2
3
4
5
Indoor unit option checking (1)
3
6
Indoor unit option checking (2)
Samsung Electronics
(cont.)
(cont.)
Function
Cooling/Heating selection
Use of wireless remote controller
MAIN/SUB wired remote controller
Temperature unit
Temperature sensor selection
Use of average temperature
Use of Auto mode
Temperature display
AC On/Off button function
Lock of Blade1
Lock of Blade2
Lock of Blade3
Lock of Blade4
Use of By-Pass mode
Use of Auto mode
Use of air purification mode
Use of external control
Temperature control reference
Temperature compensation value
Number of indoor units
Number of ERVs
Temperature increment/decrement (°C only)
Factory option setting
Software code
Software version
Indoor unit room temperature
Indoor unit EVA IN temperature
Indoor unit EVA OUT temperature
Indoor unit EEV step
Use of central control
Use of drain pump
Use of electric heater
Use of hot water coil
Use of external control
Use of RPM compensation
Heating temperature compensation
EEV stop step in heating
Data
Factory
bit
1
2
3
4
1
2
3
4
5
1
2
3
4
1
2
3
4
1,2,3
4,5,6
1,2
3,4
1
1
1~6
1~6
1,2,3
1,2,3
1,2,3
1,2,3
1
2
3
4
1
2
Filter time
3
4
5
Description
setting
0 – Cooling/Heating,
0
1 – Cooling only
1
0 – No use, 0 - Use
0
0 –MAIN, 1- SUB
0
0 – Celcius(°C), 1 – Fahrenheit(°F)
0 – Indoor unit,
0
1 – Wired remote controller
0
0 – No use, 0 - Use
1
0 – No use, 0 - Use
0 – Set temperature,
0
1 - Room temperature
0 – Indoor unit + ERV,
0
1 – Indoor unit only,
2 – ERV only,
0
0 – Unlock, 1 – lock
0
0 – Unlock, 1 – lock
0
0 – Unlock, 1 – lock
0
0 – Unlock, 1 – lock
0
0 – No use, 1 - Use
0
0 – No use, 1 - Use
0
0 – No use, 1 - Use
0
0 – No use, 1 - Use
0
-9 ~ 40(°C)
0
-9.9 ~ 9.9(°C)
-
0 ~ 16
-
0 ~ 16
0
0-1°C, 1-0.5°C, 2-0.1°C
0 – Unchanged
0
1 – Factory setting
-
Software code
-
Software version
-
Room temperature
-
EVA IN temperature
-
EVA OUT temperature
-
EEV step
-
0 – No use, 1 - Use
-
0 – No use, 1 - Use
-
0 – No use, 1 - Use
-
0 – No use, 1 - Use
-
0 – No use, 1 - Use
-
0 – No use, 1 - Use
-
0 – 2000 hours, 1 – 1000 hours
-
0-2°C, 1-5°C
-
0 – 1/80 steps, 1 – 80
Product Specifications