4.14 Discharge Pipe Temperature Control

F3
Remote
Controller
Display
Method of
An error is determined with the temperature detected by the discharge pipe thermistor.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.04
Refer to P.94
Check No.06
Refer to P.96
Check No.11
Refer to P.98
Service Diagnosis
If the temperature detected by the discharge pipe thermistor rises above
compressor stops.
The error is cleared when the temperature is dropped below
(°C)
(°C)
110
95
If the error repeats 6 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 06
Check the thermistors.
OK
Check No. 04
Check the electronic
expansion valve.
OK
Check No. 11
Check the refrigerant
line.
OK
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
Troubleshooting
°C, the
°C.
Replace the
defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7141)