DESCRIPTION
Capacity Control
Proportional Inc Band
Proportional DEC Band
Proportional ECW Gain
Guide Vane Travel Limit
Diffuser Control
Diffuser Option
Guide Vane 25% Load Pt
Diffuser 25% Load Point
Guide Vane 50% Load Pt
Diffuser 50% Load Point
Guide Vane 75% Load Pt
Diffuser 75% Load Point
Diffuser Full Span mA
VFD Speed Control
VFD Gain
VFD Increase Step
VFD Minimum Speed
VFD Maximum Speed
19XRV PIC III SETUP2 TABLE CONFIGURATION SHEET
STATUS
2 to 10
2 to 10
1 to 3
30 to 100
0/1
0 to 78
0 to 100
0 to 78
0 to 100
0 to 78
0 to 100
15 to 22
0.1 to 1.5
1 to 5
65 to 100
90 to 100
UNITS
%
DSABLE/ENABLE
%
%
%
%
%
%
mA
%
%
%
CL-8
DEFAULT
VALUE
6.5
6.0
2.0
80
DSABLE
25
0
50
0
75
0
18
0.75
2
70
100