Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 15

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

INTERNATIONAL CHILLER VISUAL CONTROLLER
(ICVC) — The ICVC is the "brain" of the PIC III system. This
module contains all the operating software needed to control
the chiller. The ICVC is mounted to the control panel (Fig. 10)
and is the input center for all local chiller set points, schedules,
configurable functions, and options. The ICVC has a stop
button, an alarm light, four buttons for logic inputs, and a
backlight display. The backlight will automatically turn off
after 15 minutes of non-use. The functions of the four buttons
or "softkeys" are menu driven and are shown on the display
directly above the softkeys.
The viewing angle of the ICVC can be adjusted for opti-
mum viewing. Remove the 2 bolts connecting the control panel
to the brackets attached to the cooler. Place them in one of the
holes to pivot the control panel forward to backward to change
the viewing angle. To change the contrast of the display, access
the adjustment on the back of the ICVC. See Fig. 10.
The ICVC features 4 factory programmed languages:
English (default)
Chinese
Japanese
Korean
OIL RECLAIM
SIGHT GLASS
DIFFUSER PRESSURE
AND DIFFUSER ACTUATOR
CABLE (FRAME 4 & 5
COMPRESSOR ONLY)
GUIDE VALVE
ACTUATOR CABLE
COMPRESSOR DISCHARGE
TEMPERATURE SENSOR
CABLE
HIGH PRESSURE
SWITCH LOCATION
OIL COOLER THERMOSTATIC
EXPANSION VALVE (TXV) BULB
OIL HEATER TERMINAL
BOX
Fig. 9 — 19XRV Compressor Controls and Sensor Locations
NOTE: Pressing any one of the four softkey buttons will acti-
vate the backlight display without implementing a softkey
function.
The ICVC may be identified by viewing the back of the plate
on which the display is mounted. (Open the control panel door
to view.) Note any of the following distinguishing features in
Table 2.
Table 2 — Identification Features of the ICVC
COLOR
CONTROLLER
OF
PLATE
ICVC
Metallic
MOTOR TEMPERATURE
SENSOR CABLE
COMPRESSOR OIL DISCHARGE
OIL COOLER THERMOSTATIC
EXPANSION VALVE (TXV)
15
CEPL No.
OTHER
SOFTWARE
(hardware)
MARKINGS
"PIC III"
Marking
CEPL
CESR
on back
130445-02
131350-0X
of green
circuit
board
PRESSURE CABLE
BEARING TEMPERATURE
SENSOR CABLE
COMPRESSOR OIL SUMP
PRESSURE CABLE
COMPRESSOR OIL SUMP
TEMPERATURE CABLE
CABLE FROM
CONTROL PANEL
a19-1606

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents