Programming
Reduced setp increase start
(800, 1100, 1400)
Red setp increase end
(801, 1101, 1401)
78
Fig. 16: Optimum start and stop control
on
Xon
Start time set forward
Xoff
Stop time set forward
ZSP
Time switching program
TRw
Room temperature setpoint
TRx
Room temperature actual value
For a relatively small required heating output, the reduced room setpoint can be
raised for cold outside temperatures. The increase is dependent upon the outside
temperature. The lower the outside temperature is, the higher the reduced set-
point for the room temperature is raised. The start of the increase and the end
point can be set. Between these two points there is a linear increase of the "re-
duced setpoint" up to the "comfort setpoint".
Fig. 17: Reduced setpoint increase
TRwA1
Red setpoint increase start
TRwA2
Red setpoint increase end
TRK
Comfort nominal value
TRR
Room temperature reduced setpoint
TOc
Outside temperature composite
Paramount three 30-115 kW
off
TOc
396532 05.11