Programming
Function
Flow setp compensation Tv
Full charging with B36
No |Yes
Min start temp diff Q33
Excess interm circ temp del
Configuration
Heating circuit 1
Off | On
Heating circuit 2
Off | On
Heating circuit 3
Off | On
DHW sensor
DHW sensor B3 | Thermostat
DHW controlling element Q3
No charging request | Charging pump | Diverting valve
Basic pos DHW div
Last request | Heating circuit | DHW
DHW separate circuit
Off | On
Contact type DHW div valve
Position on DHW | Position on HC
Ctrl boiler pump/DHW valve
All requests | Request HC1/DHW only
Solar controlling element
Charging pump | Diverting valve
External solar exchanger
Commonly | DHW storage tank | Buffer storage tank
Combi storage tank
No |Yes
Relay output QX1
None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump
Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 |
Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System
pump Q14 | Heat gen shutoff valve Y4 | Solid fuel boiler pump Q10 |
Time program 5 K13 | Buffer return valve Y15 | Solar pump ext exch
K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18 | Swim-
ming pool pump Q19 | Cascade pump Q25 | St tank transfer pump
Q11 | DHW mixing pump Q35 | DHW interm circ pump Q33 | Heat re-
quest K27 | Heat circuit pump HC1 Q2 | Heat circuit pump HC2 Q6 |
DHW ctrl elem Q3 | Status output K35 | Status information K36 | Flue
gas damper K37 | Fan shutdown K38
Relay output QX2
Parameters see Relay output QX1 (prog.-no. 5890)!
Relay output QX3
Parameters see Relay output QX1 (prog.-no. 5890)!
58
Paramount three 30-115 kW
Prog.
Standard value
1)
Level
no.
5145
E
30 s
5146
E
No
5148
E
-3°C
5151
E
30 s
5710
C
ON
5715
C
Off
5721
C
Off
5730
E
DHW sensor B3
5731
F
Charging pump
5734
E
Heating circuit
5736
E
Off
5737
E
Position on DHW
5774
E
All requests
5840
E
Charging pump
5841
E
Commonly
5870
E
No
5890
C
Alarm output K10
5891
C
Heat circuit pump HC1
Q2
5892
C
DHW controlling element
Q3