Model
Heating water
Adjustment range heating water temper-
atur
Max. temp
Operating pressure min.
Gas-connected loads
Supply pressure for natural
gas
Connected loads
Supply pressure for propane
Electrical power consumption
Electrical connec-
tion
max. electr. power consumption
Heating mode
Dimensions
Boiler weight
Boiler water con-
tent
Height
Width
Depth
Connections
Gas connection
Heating flow
Heating return
396532 05.11
Technical Data Paramount Three 30-115
Paramount three
bar
MPa
max.
bar
MPa
mbar
Natural gas
m³/h 0,59-3,20 0,95-4,00 1,48-6,10 2,22-8,10 2,12-10,1
[H
9,45 kWh/m³]
UB
mbar
Propane
kg/h 0,44-2,33 0,70-2,95 1,09-4,51 1,63-5,98 2,33-7,38 2,72-8,94
[H
12,87 kWh/kg]
U
Propane
m³/h 0,23-1,22 0,37-1,54 0,57-2,35 0,85-3,13 1,22-3,86 1,42-4,67
[H
24,64 kWh/m³]
U
V/Hz
protective mode
mm
mm
mm
Paramount three 30-115 kW
30
40
°C
°C
3,0
0,3
W
55
70
W
3
3
kg
53
53
l
3,6
3,6
407
407
3/4"
1"
1"
60
80
20 - 85
100
1,0
0,1
4,0
0,4
min. 18 - max. 25
min. 42,5 - max. 57,5
230 V / 50 Hz
100
108
170
3
3
61
72
4,7
5.8
7,8
852
480
447
542
570
1"
1 1/2"
1 1/2"
95
115
2,65-12,20
0
200
3
3
84
84
7,8
570
13