Programming
Function
Pump modulation
None | Demand | Boiler setpoint |Temp differential nominal | Burner
output
Pump speed min
Pump speed max
Output nominal
Output basic stage
Output at pump speed min
Output at pump speed max
Max fan output heating operation
Max fan output heating full charging
Fan output DHW max.
Fan shutdown heating mode
Off | On
Fan shutdown delay
Controller delay
Off | Heating mode only | DHW mode only | Heating and DHW mode
Fan output controller delay
Controller delay duration
54
Paramount three 30-115 kW
Prog.
Standard value
1)
Level
no.
2320
E
Demand
2322
E
10%
2323
E
100%
2330
E
30: 30 kW
40: 38 kW
60: 58 kW
80: 77 kW
95: 95 kW
115: 115 kW
2331
E
30: 6 kW
40: 9 kW
60: 14 kW
80: 21 kW
95: 20 kW
115: 25 kW
2334
E
0%
2335
E
100%
2441
E
30: 30 kW
40: 38 kW
60: 58 kW
80: 77 kW
95: 95 kW
115: 115 kW
2442
E
30: 30 kW
40: 38 kW
60: 58 kW
80: 77 kW
95: 95 kW
115: 115 kW
2444
E
30: 30 kW
40: 38 kW
60: 58 kW
80: 77 kW
95: 95 kW
115: 115 kW
2445
E
Off
2446
E
3 s
2450
E
Heating mode only
2452
E
30: 10,0 kW
40: 14,0 kW
60: 22,5 kW
80: 34,5 kW
95: 36,0 kW
115: 40,0 kW
2453
E
40 s
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
*)
396532 05.11