Acceleration And Deceleration Time (Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 110, Pr. 111) - Mitsubishi Electric FR-V500 Instruction Manual

High precision & fast response vector inverter
Hide thumbs Also See for FR-V500:
Table of Contents

Advertisement

Basic functions (Pr. 0 to Pr. 9)
Parameter
4
Multi-speed setting (high speed)
Multi-speed setting
5
(middle speed)
6
Multi-speed setting (low speed)
Multi-speed setting
24 to 27
(speeds 4 to 7)
Multi-speed setting
232 to 239
(speeds 8 to 15)
<Setting>
• Set the running speeds in the corresponding parameters.
Each speed can be set as desired in the range 0 to 3600r/min during inverter operation.
With any multi-speed setting parameter being read, press
In this case, press
SET
Pressing
reflects the preset speed.
SET
REMARKS
• Press
when the FR-PU04V (option) is used.
WRITE
• Use Pr. 180 to Pr. 183 and Pr. 187 to assign the terminals used for signals RH, RM, RL, and REX. (*)
*Changing the terminal assignment using Pr. 180 to Pr. 183, Pr. 187 (input terminal function selection) may affect the other
functions. Please make setting after confirming the function of each terminal.
• The priorities of the external terminals for speed commands are as follows.
Jog > pulse train input (option FR-A5AP) > digital setting (option FR-A5AX) > multi-speed operation > PID > terminal 2
CAUTION
1. The multi-speed settings override the main speed (across terminals 2-5).
2. The multi-speeds can also be set in the PU or external operation mode.
3. For 3-speed setting, if two or more speeds are simultaneously selected, priority is given to the preset
speed of the lower signal. (RL > RM > RH)
4. Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
5. The settings can also be changed during operation.
6. When the jog signal is used with multi-speed signals, the jog signal has priority.
Related parameters
• Maximum, minimum speed setting ⇒ Pr. 1 "maximum speed", Pr. 2 "minimum speed" (Refer to page 76.)
• Signal RH, RM, RL, REX terminal assignment ⇒ Pr. 180 to Pr. 183, Pr. 187 (input terminal function selection) (Refer to page 150.)
• External operation mode setting ⇒ Pr. 79 "operation mode selection" (Refer to page 117.)
• Extended mode/simple mode setting ⇒ Pr. 160 "extended function selection" (Refer to page 150.)
3.3.5
Acceleration and deceleration time
(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 110, Pr. 111
Set the acceleration/deceleration time of the motor
during speed control and position control by
parameter setting.
Set a larger value for a slower speed increase/
decrease or a smaller value for a faster speed
increase/decrease.
Under torque control, the speed limit value varies
with the acceleration/deceleration time.
Name
Factory Setting
to store the preset speed. (This is also enabled in the external mode.)
Setting Range
1500r/min
0 to 3600r/min
750r/min
0 to 3600r/min
150r/min
0 to 3600r/min
0 to 3600r/min,
9999
9999
0 to 3600r/min,
9999
9999
to change the setting.
speed
Pr.20
Acceleration
Pr.7
Pr.44
Acceleration
Pr.110
time
78
Remarks
Simple mode
Simple mode
Simple mode
"9999" No setting
"9999" No setting
)
torque
position
Running speed
(speed limit value)
Constant
Time
speed Deceleration
Pr.8
Pr.45
Deceleration
Pr.111
time