4.6 3D auto operation
Control the flap and louver by 3D AUTO button on the wireless remote control.
Air flow selection and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned.
(1) During Cooling and Heating (Including auto cooling and heating)
(a) Air flow selection is determined according to room temperature and setting temperature.
Operation mode
At cooling
At heating
(b) Air flow direction is controlled according to the room temperature and setting temperature.
1)
When 3D auto operation starts
Flap
Louver
When Room temp. – Setting temp. is ≤ _ 5ºC during cooling and when Setting temp. – Room temp. is ≤ _ 5ºC during
2)
heating, the system switches to the following air flow direction control. After the louver swings left and right symmetrically
for 3 cycles, control is switched to the control in 3).
Flap
Louver
3)
After the flap swings for 5 cycles, control is switched to the control in 4).
Flap
Louver
4)
For 5 minutes, the following air flow direction control is carried out.
Flap
Louver
5)
After 5 minutes have passed, the air flow direction is determined according to the room temperature and setting
temperature.
Operation mode
At cooling
At heating
(2) During DRY Operation (including auto DRY operation)
Air flow selection
Flap
Louver
Room temp. – Setting temp. >5˚C
HIGH POWER
Setting temp. – Room temp. >5˚C
HIGH POWER
Cooling
Wide (fixed)
Cooling
Horizontal blowing (Fixed)
Cooling
Cooling
Horizontal blowing (Fixed)
Room temp. – Setting temp. ≤ _ 2˚C
The control in 4) continues.
Setting temp. – Room temp. ≤ _ 2˚C
The control in 4) continues.
According to DRY operation.
Horizontal blowing (Fixed)
Air flow selection
AUTO
Room temp. – Setting temp. ≤ _ 5˚C
AUTO
Setting temp. – Room temp. ≤ _ 5˚C
AUTO
Heating
Up/down Swing
Center (fixed)
Heating
Slant forwardl blowing (Fixed)
Left/right Swing
Heating
Up/down Swing
Center (Fixed)
Heating
Slant forwardl blowing (Fixed)
Wide (Fixed)
Air flow direction contorol
2˚C < Room temp. – Setting temp. ≤ _ 5˚C
Control returns to the control in 2).
2˚C < Setting temp. – Room temp. ≤ _ 5˚C
Control returns to the control in 2).
Wide (Fixed)
15
-
-
HI
MED
LO
HI
MED
LO
Room temp. – Setting temp. > 5˚C
Control returns to the control in 1).
Setting temp. – Room temp. > 5˚C
Control returns to the control in 1).