Combination Of Indoor And Outdoor Combustion Air - Prestige Solo 175 Installation And Maintenance Manual

Table of Contents

Advertisement

Combustion Air and Venting
Fig. 2:
All Combustion Air from outdoors
through; One Permanent Air
Openings
Two Permanent Openings Method.
Two permanent openings, one commencing
within 12 in. of the top and one commencing
within 12 in. of the bottom of the enclosure,
shall be provided. The openings shall commu-
nicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the out-
doors, as follows:
-
Where directly communicating with the
outdoors or where communication to the
outdoors is through vertical ducts, each
opening shall have a minimum free area
of 1 sq. in./4000 Btu/hr of total input rat-
ing of all equipment in the enclosure.
See Fig.3.
-
Where communicating with the out-
doors is through horizontal ducts, each
opening shall have a minimum free
area of not less than 1 sq.in./2000
Btu/hr of total input rating of all equip-
ment in the enclosure. See Fig. 4.
Fig. 3:
All Combustion Air from Outdoors
Through Ventilated Attic
All Combustion Air from Outdoors
Fig. 4:
through Horizontal Ducts
Combination of Indoor and Outdoor
Combustion Air
Indoor Openings: Where used, openings con-
necting the interior spaces shall comply with
the Indoor Combustion Air section on page 7.
8