Installation Instructions
"A"
01 Zn List
1
"B"
01 Enter Zn type
Perimeter
03
"C"
01 Enter Zn No.
12
01 Output Action
Close for 2 sec
1
Enter Output No.
R02
02
02
A E P TRIG
R02 1 1
3
ZL=1
5-8
If zone list was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone list number associated with this output number:
01-08 = zone list (Do not use pager zone list 09 in output definitions)
Enter the zone list event that will activate this output:
0 = restore; 1 = alarm;
Enter Event
2 = fault; 3= trouble
Alarm
1
For alarm, fault, and trouble, an event on ANY zone in the list activates the output,
NOTE:
but ALL zones in the list must be restored before the output is restored.
Press [∗] to continue and skip to the "Output Action" prompt.
If zone type was selected, this screen appears. Otherwise skip to the next prompt.
Enter the desired zone type for this output number.
CHOICES FOR ZONE TYPES:
00 = Not Used
05 = Trouble Day/Alarm Night
01 = Ent/Exit #1
06 = 24 Hr Silent
02 = Ent/Exit #2
07 = 24 Hr Audible
03 = Perimeter
08 = 24 Hr Aux
04 = Interior Follower 09 = Fire
10 = Interior w/Delay
CHOICES FOR SYSTEM OPERATION:
20 = Arming–Stay
36 = At Bell Timeout***
21 = Arming–Away
38 = Chime
22 = Disarming
39 = Any Fire Alarm
31 = End of Exit Time
40 = Bypassing
32 = Start of Entry Time 41 = AC Power Failure
33 = Any Burglary Alarm 42 = System Battery Low
43 = Comm. Failure
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu Mode to assign the function key (function "07").
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device NN.
Code + # + 8 + NN Key Entry stops Device NN.
Press [∗] to continue and skip to the "Output Action" prompt.
If zone number was selected, this screen appears.
Enter the desired zone number associated with this output number.
Press [∗] to continue.
Enter the zone event that will activate this output.
01 Enter Event
0 = restore; 1 = alarm/fault/trouble
Restore
0
Press [∗] to continue to the "Output Action" prompt
Enter the desired device action as listed below.
0 = off
1 = Close for 2 seconds
2 = Close and Stay Closed
3 = Continuous Pulse on & off (1 sec ON, 1 sec OFF)
Press [∗] to continue.
Enter the device output number (programmed in *79 Menu Mode) you want associated with
this output.
01-04 = output no.
17-18 = on-board triggers
Press [∗] to continue.
A summary screen appears showing the programmed settings.
Press [∗] to return to output function number prompt.
12 = Monitor Zone
14 = Carbon Monoxide
16 = Fire w/verification
23 = No Alarm Response
24 = Silent Burglary
77 = keyswitch zone
81 = AAV Monitor Zone
90 = Configurable
52 = Kissoff
54 = Fire Zone Reset
58 = Duress
60 = AAV
66 = Function Key†
67 = Bell Fail
68 = Telco line cut
78 = keyswitch red LED
79 = keyswitch green LED
4 = Change Device State
5 = Duration 1 (see data field *177)
6 = Duration 2 (see data field *177)