Toshiba RAS-10G2KVP-E Service Manual page 99

Split type
Table of Contents

Advertisement

11-8. Trou bleshooting
11-8-1. How to Check Whether the Air Purifier and Minus Ion Gerneration are Good or NG
Turn off the power breaker once,
and turn on again after 10 seconds.
Does the OPERATION indicator flash?
YES
Turn off the power breaker and remove
CN401 (Micro switch connector).
Short-circuit between
of CN401 at PC side, and turn on the
power breaker after 10 seconds.
Short Timer and then check,
Is DC12V applied between
(GND) of CN1 of the
2
high-voltage generator?
YES
Is there conduction of
micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
NO
Is there conduction of
micro-switch connector under
ON status of the micro-switch
(Front panel closed)?
YES
1) Check operation while short-circuiting CN401 of the main P.C. board.
2) Perform air purifying operation by the remote controller.
• In this time, check that the remote controller is in status which is shortened by time on
the reactivation preventive timer and all display indicators go on for approx. 3 seconds
when a signal is received.
If time on the reactivation preventive timer is not shortened,
(
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
(Because the power ON/OFF is controlled on the program)
3) Be sure not to touch the electric dust collector, ionizer, or ionized wire unit with the human body.
Does the indoor fan rotate?
YES
Does the PURE indicator (white)
go on?
YES
Are the electric dust
collector and ionizer dried?
(Electrode check)
YES
Refer to items, cleaning and check
for the electric dust collector/ionizer/
ionized wire units.
When the ionized wire is
(
disconnected or when dirt is
not cleaned even cleaned,
replace each unit.
NO
1
and
2
pin
NO
(DC12V)
between
1
YES
NO
Micro-switch malfunction
NO
NO
Dry the electric
NO
dust collector
and ionizer.
Referring to the right figure, check the
high-output voltage of the air filter unit.
(NOTE)
Use an exclusive high voltage tester;
otherwise the tester may be broken.
Is output of the ionizer
approx. -5.7 kV to -6.5 kV?
Is output of the collector
approx. -2.7 kV to -3.4 kV?
)
collector/ionizer/ionized
YES
(cracking noise) heard
Is DC12V applied
(+) and
(–)
1
2
of CN402 of the main
P.C. board ?
YES
Micro-switch is stuck
Is DC-5V to DC-10V
applied between
(Negative voltage)
4
and
(GND)
2
of CN402 of the main
P.C. board?
YES
YES
YES
Are the electric dust
wire units dirty?
Is an abnormal sound
from the electrode?
98
FILE NO. SVM-14017
To item "Power supply is not turned on"
NO
Replace the main P.C. board.
Replace micro-switch.
• Conduction check of micro-switch
ON
)
Tester
To item "Only indoor fan does not operate"
NO
Check High Voltage output Short to GND?
• How to check output of the air purifier
<Caution on High Voltage!!>
Be sure not to come
to contact to the gray
part or not to touch
the ionized cables.
NO
Replace the high-voltage generator.
NO
No trouble
Push the switch
ON
Release the switch
OFF