Power Selection Mode; Outdoor Quiet Control - Toshiba RAS-10G2KVP-E Service Manual

Split type
Table of Contents

Advertisement

Item
Operation flow and applicable data,etc
([POWER-SEL] button on the remote controller
21. POWER
is pressed)
Selection
Mode
− Power Selection 75% is 75% of maximum
current.
− Power Selection 50% is 50% of rate maximum
current.
POWER-SELECTION OPERATION
POWER SEL
[100%]
<With Quiet control/Non-select method>
22. Outdoor
Quiet
control
Select "Conrol" or "No conrol" by keeping
[RESET] button pushed for 20 seconds.
("No control" at shipment from the factory.)
Exchanging from "No control" to "Control" :
Beep sound is heard (Pi, Pi, Pi, Pi, Pi) and
the operation LED 5Hz flashes for 5
seconds.
Exchanging from "Control" to "No control" :
Beep sound is heard.
(Operation LED does not flash.)
<Maximum number of revolution of compressor at normal time and Quiet control time>
Outside temp. Normail time Ouiet controlled Normail time Ouiet controlled Normail time Ouiet controlled
(TO)
COOL
~ 5°C
HEAT
~ 10°C-5°C
- 10°C ~
POWER SEL
POWER SEL
POWER SEL
[75%]
[50%]
RAS-10G2KVP-E
(rps)
(rps)
61
53
93
73
93
73
93
73
1. Purpose
The function is used when its circuit
breaker is shared with other electrical
appliances. It limits the maximum
current/ power consumption to 100%,
75% or 50%.
The lower the percentage, the higher
the saving and also the longer the
compressor lifetime.
2. Description
When the level is selected, Power-SEL
level flashes on LCD display for 3
seconds. In case of 75% and 50%
level, number "75" or "50" also flashes
for 2 seconds.
[100%]
Note : Due to the reason that POWER
1. Purpose
For the users who concern about noise
of the outdoor unit, this control controls
the max. revolutions of the compressor
to reduce the noise.
2. Description
To reduce noise, [RESET] button of the
indoor unit is kept pushed for 20
seconds.
The number of revolution for the indoor
fan motor and the seup temp value are
kept as they are.
3. Operation
As shown in the table, the maximum
revolution number of indoor unit
compressor can be reduced.
As the maximum number of revolution
of the compressor is restricted, the rise-
up performance at the start time is
weakened.
RAS-13G2KVP-E
(rps)
(rps)
58
58
73
73
73
73
73
73
− 47 −
FILE NO. SVM-14017
Description
SELECT FUNCTION limits the
maximum current, inadequate
capacity may occur.
RAS-16G2KVP-E
(rps)
78
80
80
80
.
(rps)
64
76
76
76