DP6060 Dual-Input Process Meter

F4 Digital Input Connections

A digital input, F4, is standard on the meter. This digital input connected
with a normally open closure across F4 and COM, or with an active low
signal applied to F4.

Figure 15. F4 Digital Input Connections

4-20 mA Output Connections

Connections for the 4-20 mA transmitter output are made to the
connector terminals labeled MA OUT. The 4-20 mA output may be
powered internally or from an external power supply.
RELAY1
3
2
4-20 mA Input
Remote Display,
Chart Recorder, Etc.

Figure 16. 4-20 mA Output Connections

Analog Output Transmitter Power Supply

The internal 24 VDC power supply powering the analog output may be
used to power other devices, if the analog output is not used. The I+
terminal is the +24 V and the R terminal is the return.
24 V
MA OUT
R
I-
I+
1
3
2
1
-
+
RELAY1
3
2
-
+
4-20 mA
Input Meter
26
Instruction Manual
24 V
MA OUT
R
I-
I+
1
3
2
1
-
+
12-35 VDC