Normal operation – Stage 3 – Refrigeration start
Seconds later the C LEDs come on and the coils of both of the relays are energized, closing their normally
open contacts. This completes the circuit to the coil of the liquid line solenoid valve. The valve opens increasing
the pressure in the suction line. The low-pressure control then starts the condensing unit. As the gearmotors
reach normal speed the current relays re-open, dropping out their start windings. The icemaker is now in normal
icemaking mode.
115 VAC
60 HZ
x
GREEN
BLACK
WHITE
WHITE
GEAR MOTOR
GEAR MOTOR
ELECTRICAL BOX
POWER
SWITCH
BLACK
BLACK
WHITE
1
3
4
6
7
9
A
B
BLUE
PURPLE
WHITE
WHITE
1
3
4
6
7
9
A
B
BLUE
RED
Solenoid Valve
WTR PROBE
L1
L2
RESET
COMP
FAN
DRV
BIN LOW V
HP SW
COMP
WTR PROBE
L1
L2
RESET
COMP
FAN
DRV
BIN LOW V
HP SW
COMP
19
PWR
WATER
SENSOR
DR
C
COMPRESSOR
20M
SWITCH
60M
2ND
WTR
B-T
B-E
HIGH VOLTAGE BIN
WHITE
PWR
SIGNAL
DR
C
20M
60M
2ND
WTR
BIN
B-T
SIGNAL
SWITCH
B-E
HIGH VOLTAGE BIN
BIN
CORD