VenTInG InSTallaTIon
For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18"
(457 mm). This does not apply if the 45° elbows are
installed on the vertical part of the vent system.
The maximum number of elbow degrees in a system is
270°. Figure 17
Example:
Elbow 1 =
Elbow 2 =
Elbow 3 =
Elbow 4 =
Total Angular Variation =
1
2
3
4
24" (610 mm)
Minimum
Figure 17 -
Maximum Elbow Usage
Below GraDe InSTallaTIonS
When it is not possible to meet the required vent terminal
clearances of 12" above grade level, a snorkel kit is recom-
mended. It allows installation depth down to 7" (178 mm)
below grade level. The 7" (178 mm) is measured from the
center of the horizontal vent pipe as it penetrates through
the wall.
ensure that sidewall venting clearances are observed.
If venting system is installed below ground, we recom-
mend a window well with adequate and proper drainage
to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is neces-
sary. The maximum horizontal run with the 24" vertical pipe
is 36". This measurement is taken from the collar of the
fireplace (or transition elbow) to the face of the exterior wall.
See the Sidewall Venting Graph for extended horizontal
run if the vertical exceeds 24".
1. Establish vent hole through the wall.
73D4125
90°
45°
45°
90°
270°
FP1383
FP1383
Max bends
2. Remove soil to a depth of approximately 16" below base
of snorkel. Install drain pipe. Install window well (not
supplied). Refill hole with 12" of coarse gravel leaving
a clearance of approximately 4" below snorkel. Figure
18
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
7. Level the soil so as to maintain a 4" clearance below
snorkel. Figure 18
1
2
Firestop
3
4
24"
(610 mm)
Minimum
FP2134
If the foun-
d a t i o n
FP2134
i s
r e c e s s e d ,
below grade install
u s e r e c e s s
brackets (not
s u p p l i e d )
Foundation
for securing
Recess
lower portion
of the snorkel.
Fasten brack-
ets to wall first,
then secure
Watertight Seal
t o s n o r k e l
Around Pipe
with self drill-
ing #8 x 1/2
sheet metal
Figure 19 -
screws. It will
Snorkel Installation, Recessed Foundation
be necessary
to extend vent
pipes out as far as the protruding wall face. Figure 19
KSTDV Series Gas Fireplace
Screws
Minimum
4" Clearance
Ground
Gravel
Drain
Foundation
Wall
Figure 18 -

Below Grade Installation

Snorkel
Wall Screws
Sheet Metal
Screws
FP1966
FP1966
snorkel
Window
Well
17