Vertical/Horizontal Termination Locations - Vermont Castings KSTDV500 Installation And Operating Instructions Manual

Kstdv series direct vent gas fireplace
Table of Contents

Advertisement

VenTInG InSTallaTIon
General VenTInG InForMaTIon - TerMInaTIon locaTIon
Figure 8 -
Termination Locations
A = Clearance above grade, veranda, porch,
deck, or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal
distance of 2' (610mm) from the center
line of the terminal
E = Clearance to unventilated soffit
F = Clearance to outside corner
G = Clearance to inside corner (see next page)
H = Clearance to each inside of center line
extended above meter/regulator assembly
I = Clearance to service regulator vent outlet
J = Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to any
other appliances
K = Clearance to a mechanical air supply inlet
L = Clearance above paved sidewalk or paved
driveway located on public property
M = Clearance under veranda, porch, deck or
balcony
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family
dwellings and serves both dwellings
 only permitted if veranda, porch, deck or balcony is fully open on a
minimum 2 sides beneath the floor:
73D4125
D
E
L
C
B
V
Fixed
Closed
F
V
B
CFM145a
VENT TERMINATION
V
12" (30 cm)
6" (15 cm) for appliances
< 10,000BTU/h (3kW), 12" (30 cm)
for appliances > 10,000 Btuh (3kW) and
< 100,000 BTU/h (30kW), 36" (91 cm)
for appliances > 100,000 BTU/h (30kW)
12" (305 mm) recommended to
prevent window condensation
18" (458 mm)
12" (305 mm)
see next page
see next page
3' (91 cm) within a height of 15' (5 m)
above the meter/regulator assembly
3' (91 cm)
6" (15 cm) for appliances < 10,000
BTU/h (3kW), 12" (30 cm) for
appliances > 10,000 BTU/h (3kW) and
< 100,000 Btuh (30kW), 36" (91 cm)
for appliances > 100,000 BTU/h (30kW)
6' (1.83 m)
7' (2.13 m)†
12" (30 cm)
INSIDE
CORNER DETAIL
G
V
A
B
B
V
V
Fixed
Operable
Closed
B
X
V
J
B
A
AREA WHERE TERMINAL IS NOT PERMITTED
X
AIR SUPPLY INLET
canadian Installations
CFM145a
DV Termin Location
5/01/01 Rev. 12/05/01
sta
NOTE: 1. Local codes or regulations may require different
clearances.
2. The special venting system used on Direct Vent Fireplaces
are certified as part of the appliance, with clearances
tested and approved by the listing agency.
3. Vermont Castings Group assumes no responsibility for the
improper performance of the appliance when the venting
system does not meet these requirements.
KSTDV Series Gas Fireplace
H
M
I
K
X
V
1
uS Installations
12" (30 cm)
6" (15 cm) for appliances
< 10,000 BTU/h (3kW), 9"
(23 cm) for appliances > 10,000
Btuh (3kW) and < 50,000 BTU/h
(15kW), 12" (30 cm) for
appliances > 50,000 BTU/h(15kW)
12" (305 mm) recommended to
prevent window condensation
18" (458 mm)
12" (305 mm)
see next page
see next page
3' (91 cm) within a height of 15'
(5 m) above the meter/regulator
assy
3' (91 cm)
6" (15 cm) for appliances
< 10,000 BTU/h (3kW), 9"
(23 cm) for appliances > 10,000
BTU/h (3kW) and < 50,000 BTU/h
(15kW), 12" (30 cm) for
appliances > 50,000 BTU/h(15kW)
3' (91 cm) above if within 10'
(3 m) horizontally
7' (2.13 m)†
12" (30cm)