Below Grade Installation - Vermont Castings WDV500NTSC Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

WDV Series Gas Fireplace
Example:
Elbow 1 =
Elbow 2 =
Elbow 3 =
Elbow 4 =
Total Angular Variation =
1
2
3
4
12"
Minimum
Figure 17 -
Maximum Elbow Usage
BelOW GraDe InstallatIOns
When it is not possible to meet the required vent terminal
clearances of 12" above grade level, a snorkel kit is recom-
mended. It allows installation depth down to 7" (178 mm)
below grade level. The 7" (178 mm) is measured from the
center of the horizontal vent pipe as it penetrates through
the wall.
ensure that sidewall venting clearances are observed.
If venting system is installed below ground, we recom-
mend a window well with adequate and proper drainage
to be installed around the termination area.
If installing a snorkel, a minimum 12" vertical rise is neces-
sary. The maximum horizontal run with the 12" vertical pipe
is 36". This measurement is taken from the collar of the
fireplace (or transition elbow) to the face of the exterior wall.
See the Sidewall Venting Graph for extended horizontal
run if the vertical exceeds 12".
1. Establish vent hole through the wall.
2. Remove soil to a depth of approximately 16" below base
of snorkel. Install drain pipe. Install window well (not
supplied). Refill hole with 12" of coarse gravel leaving
a clearance of approximately 4" below snorkel. Figure
18
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
16
90°
45°
45°
90°
270°
FP1180
FP1180
max bends
7. Level the soil so as to maintain a 4" clearance below
snorkel. Figure 18
Screws
Firestop
1
2
3
12"
4
Minimum
FP2134
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
FP2134
brackets to wall first, then secure to snorkel with self drill-
below grade install
ing #8 x 1/2" sheet metal screws. It will be necessary to
extend vent pipes out as far as the protruding wall face.
Figure 19
Foundation
Recess
Watertight Seal
Around Pipe
Figure 19 -
Snorkel Installation, Recessed Foundation
FP1966
snorkel
Do not back fill around snorkel.
a clearance of at least 4" must be
maintained between the snorkel and
the soil.
VentInG InstallatIOn
Minimum
4" Clearance
Ground
Window
Well
Gravel
Drain
Foundation Wall
Figure 18 -

Below Grade Installation

Snorkel
Wall Screws
Sheet Metal
Screws
78D0011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wdv500ptscWdv600ptscWdv600ntsc

Table of Contents