3.1.7 Centralized Control Group No. Setting
! If carrying out centralized control by central remote controller or unified ON/OFF
BRC1A Type
! Group No. setting by remote controller for centralized control
1. When in the normal mode, push the
2. Set mode No. "00" with the
3. Push the
4. Set the group No. for each group with the
5. Push the timer
6. Push the
! Even if not using a remote controller, connect the remote controller when setting the group
! Set the group No. after turning on the power supply for the central remote controller, unified
! Group No. setting by wireless remote controller for centralized control
BRC7C Type
1. When in the normal mode, push
2. Set mode No. "00" with
3. Set the group No. for each group with
4. Enter the selected group numbers by pushing
5. Push
BRC7C Type
Test Operation
controller, group No. must be set for each group individually by remote controller.
then enters the "field setting mode."
button to inspect the group No. display.
manner of 1-00, 1-01, ...,1-15, 2-00,...4-15. However, the unified ON/OFF controller
displays only the group No. within the range selected by the switch for setting each address.)
button to define the selected group No.
button to return to the normal mode.
Group No.
No., set the group No. for centralized control, and disconnect after making the setting.
ON/OFF controller, and indoor unit.
enters the "field set mode."
button and return to the normal mode.
button for 4 seconds or more, and operation
button. ∗
button (The group No. increases in the
button for 4 seconds or more, and operation then
button.
button (advance/backward).
Mode No.
Field Set Mode
Group No.
Mode No.
Field Set Mode
button.
Field Setting