Daikin R-410A Service Manual page 128

Vrv ii-sr-410a heat pump 50hz
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
∗1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
": Continuity
×: No continuity
118
Pin No.
1. White
2. Yellow
3. Orange
"
×
Approx.
300Ω
×
SiBE39-402A
4. Blue
5. Red
"
×
Approx.
150Ω
"
×
Approx.
300Ω
"
×
Approx.
150Ω
×
Troubleshooting
6. Brown
×
"
Approx.
150Ω
×
"
Approx.
150Ω
×

Hide quick links: