Field Setting
$
Setting
Setting
Setting No. indication
No.
contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
22
Night-time
"
)
low noise
setting
25
External
low noise
setting
26
Night-time
low noise
start setting
27
Night-time
low noise
end setting
29
Capacity
precedence
setting
30
Demand
setting 1
32
Continuous
demand
setting
12
External
low noise /
Demand
setting
Setting mode indication section
3.3.3 Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
indoor and outdoor units
Both the outdoor unit and the indoor unit are forbidden to operation.
[Operation procedure]
$ In setting mode 2 with units in stop mode, set "B Refrigerant Recovery / Vacuuming mode"
% Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
& Press Mode button "BS1" once and reset "Setting Mode 2".
94
%
)
)
)
)
)
"
"
"
"
"
"
"
"
to ON. The respective expansion valve of indoor and outdoor units are fully opened. (H2P
turns to display "TEST OPERATION" (blinks), "TEST OPERATION" and "IN CENTRALIZED
CONTROL" are displayed on the remote controller, and the operation is prohibited.
refrigerant recovery unit for more detal.)
Setting No. indication
)
"
)
"
"
)
)
"
"
)
)
"
)
"
"
)
"
)
)
"
"
)
"
"
)
"
"
"
)
"
)
"
"
"
"
)
)
)
)
)
)
)
)
)
"
"
)
)
Setting No. indication section
&
Setting
Setting contents indication (Initial setting)
contents
H1P H2P H3P H4P H5P H6P H7P
OFF
"
)
)
)
(Factory
setting)
"
)
)
)
Mode 1
"
)
)
)
Mode 2
"
)
)
)
Mode 3
"
)
)
)
Mode 1
Mode 2
"
)
)
)
(Factory
setting)
"
)
)
)
Mode 3
"
)
)
)
PM 8:00
PM 10:00
"
)
)
)
(Factory
setting)
"
)
)
)
PM 0:00
"
)
)
)
AM 6:00
"
)
)
)
AM 7:00
AM 8:00
"
)
)
)
(Factory
setting)
Low noise
precedence
"
)
)
)
(Factory
setting)
Capacity
"
)
)
)
precedence
60 % of
"
)
)
)
rated power
consumption
70 % of
rated power
"
)
)
)
consumption
(Factory
setting)
80 % of
"
)
)
)
rated power
consumption
OFF
"
)
)
)
(Factory
setting)
Continuous
"
)
)
)
demand 1
fixed
NO
"
)
)
)
(Factory
set)
"
)
)
)
YES
Set contents indication section
SiBE39-402A
)
)
)
)
)
"
)
"
)
)
"
"
)
)
"
)
"
)
"
)
)
)
)
"
)
"
)
"
)
)
)
)
"
)
"
)
"
)
)
)
)
"
)
"
)
)
)
"
)
"
)
"
)
)
)
)
"
)
"
)
)
)
"
)
"
)
Test Operation