I-Series Ice Machine Training Manual
The head pressure control valve (headmaster) maintains adequate condensing pres-
sure during periods of low ambient temperature. The I-Series ice makers are charged
with R404A refrigerant. The headmaster valve is set to maintain a condensing pres-
sure of 200 psig (13.8 BAR) down to an operating temperature of -20°F (-6.7° C).
Touching the lines of the headmaster will determine the flow path the headmaster is
in; condenser to receive, or bypass to receiver. Installing a gauge at the receiver out-
let valve will determine if the headmaster is functioning to maintain the proper oper-
ating pressure. It should be less than 15 psi (1.0 BAR). Less pressure indicates low
refrigerant or kinked lines.
Refer to the I Series Ice Cube Machine Service Manual & Maintenance Guide for
additional head pressure control information.