Lennox XP21 Series Installation Instructions Manual page 47

Dave signature collection system
Table of Contents

Advertisement

Heat Pump Control
icomfort
icomfort
LEDs
Touch
Touch
Thermostat
Thermostat
DS15
DS13
Display
Display
Yellow
Red
4 flashes
Critical Alert
Off
then pause
Code 404
5 flashes
Critical Alert
Off
then pause
Code 405
6 flashes
Critical Alert
Off
then pause
Code 406
7 flashes
Critical Alert
Off
then pause
Code 407
8 flashes
Critical Alert
Off
then pause
Code 408
Moderate/
9 flashes
Critical Alert
Off
then pause
Code 409
Fast simultaneous flashing of DS11,
DS13, DS14 and DS15
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
3. Initially a moderate status is displayed and is escalated to critical if alarm exists for more than 10 minutes.
®
®
Possible
Possible
Condition
Condition
Cause(s)
Cause(s)
Compressor has
a locked out due
to run capacitor
Locked rotor
short, bearings
are seized,
excessive liquid
refrigerant.
Compressor has
an open circuit
due to power dis-
Open circuit
connection, fuse
is open or other
similar conditions.
Current not
Open start
sensed by Start
circuit
transformer.
Current not
Open run
sensed by run
circuit
transformer.
Welded
Compressor
contactor
always runs
Secondary low
24VAC is below
3
voltage
18VAC.
OEM Mode
Factory test mode.
Solution
Solution
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at discon-
nect is low).
S
Check wiring connections
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
S
Check compressor contactor wiring and
connectors
S
Check for compressor contactor failure
(burned, pitted or open)
S
Check wiring and connectors between supply
and compressor
S
Check for low pilot voltage at compressor
contactor coil
4
High pressure switch is open and requires manual
reset.
5
Open circuit in compressor supply wiring or
connections.
6
Unusually long compressor protector reset time
due to extreme ambient temperature.
7
Compressor windings are damaged.
S
Check compressor motor winding resistance
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or
connections.
S
Check wiring and connectors between supply
and the compressor S terminal
3
Compressor start winding is damaged.
S
Check compressor motor winding resistance
1
Open circuit in compressor start wiring or
connections.
S
Check wiring and connectors between supply
and the compressor R terminal
2
Compressor start winding is damaged.
S
Check compressor motor winding resistance
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to mod-
ule.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at discon-
nect is low).
S
Check wiring connections
Page 47
Clearing Status
Clearing Status
Clears after
power reset or
four normal
compressor
cycles.
Clears after one
normal com-
pressor run
cycle or power
reset.
Clears when
amperage is de-
tected in RUN
and START
sensors, or after
power reset.
Clears when
amperage is de-
tected in RUN
and START
sensors, or after
power reset.
Clears after one
normal com-
pressor run
cycle or after
power reset.
Clears after volt-
age is higher
than 20VAC for
two seconds, or
after power re-
set.
XP21 SERIES

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp21−024Xp21−036Xp21−048Xp21−060