Lennox XP21 Series Installation Instructions Manual page 29

Dave signature collection system
Table of Contents

Advertisement

WEIGH IN
Use
method for adding initial refrigerant charge, and then use
refrigerant charge.
WEIGH IN
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refriger-
ant charge:
Amount specified on
nameplate
SUBCOOLING
1. Check the airflow as illustrated in figure 20 to be sure the indoor airflow is as required. (Make any air flow adjustments
2. Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge.
3. Connect gauge set.
4. Check liquid and vapor line pressures. Compare pressures with either heat or cooling mode normal operating
USE
COOLING
MODE
60ºF
(15ºC)
USE
5. Set thermostat for heat/cool demand, depending on mode being used:
HEATING
MODE
SATº
LIQº –
SCº
=
6. Read the liquid line temperature; record in the LIQº space.
7. Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart listed
8. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space.
9. Compare SCº results with tables 4 through 7, being sure to note any additional charge for line set and/or match−
10. If subcooling value is greater than shown in tables 4 through 7 for the applicable unit, remove refrigerant; if less
11. If refrigerant is added or removed, repeat steps 5 through 6 to verify charge.
12. Disconnect gauge set and re−install both the liquid and suction service valve caps.
Figure 22. Using HFC−410A Subcooling Method
CHARGING METHOD
Adjust amount. for variation in line set
length listed on line set length table below.
+
Refrigerant Charge per Line Set Length
LIQUID LINE SET DIAMETER
3/8" (9.5 MM)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this
amount.
NOTE
Insulate liquid line when it is routed through areas where the surrounding ambient temperature could
become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE
The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge
information.
Figure 21. Using HFC−410A Weigh In Method
CHARGING METHOD
before continuing with the following procedure.)
pressures in table 8, Normal Operating Pressures, High Stage.
NOTE
The reference table is a general guide. Expect minor pressure variations. Significant differences may
mean improper charge or other system problem.
USING COOLING MODE
subcooling values (second stage − high capacity) in table 8 are based on 70 to 80°F (21−27°C) indoor return air
temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode
set point to 68ºF (20ºC) which should call for second−stage (high stage) cooling. When pressures have stabilized,
continue with Step 6.
USING HEATING MODE
values (second−stage − high capacity) in table 8 are based on 65−75°F (18−24°C) indoor return air temperature;
if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode set point to
77ºF (25ºC) which should call for second−stage (high stage) heating. When pressures have stabilized, continue
with Step 6.
in table 9 and record it in the SATº space.
up.
than shown, add refrigerant.
SUBCOOLING
Additional charge specified per indoor
unit match−ups starting on page 30.
+
OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M)
3 OUNCE PER 5' (85 G PER 1.5 M)
When the outdoor ambient temperature is 60°F (15°C) and above. Target
When the outdoor ambient temperature is below 60°F (15°C). Target subcooling
High Stage (High Capacity)
Page 29
method for for verifying
=
LINE SET*
Total Charge
XP21 SERIES