System Operations - Lennox XP21 Series Installation Instructions Manual

Dave signature collection system
Table of Contents

Advertisement

°F
Psig
°F
Psig
32
100.8
48
137.1
33
102.9
49
139.6
34
105.0
50
142.2
35
107.1
51
144.8
36
109.2
52
147.4
37
111.4
53
150.1
38
113.6
54
152.8
39
115.8
55
155.5
40
118.0
56
158.2
41
120.3
57
161.0
42
122.6
58
163.9
43
125.0
59
166.7
44
127.3
60
169.6
45
129.7
61
172.6
46
132.2
62
175.4
47
134.6
INSTALLING ISOLATION GROMMETS
Locate the isolation grommets (provided). Slide grommets
onto vapor and liquid lines. Insert grommets into piping
panel to isolate refrigerant lines from sheet metal edges.
SUCTION LINE
LIQUID LINE
TWO ISOLATION GROMMETS ARE
PROVIDE FOR THE LIQUID AND
SUCTION LINE PIPE PANEL PASS
THROUGH.
REAR VIEW OF UNIT EXTERIOR
Figure 23. Isolation Grommets

System Operations

IMPORTANT
Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.
506601−01
.
Table 9
HFC−410A Temperature (°F) − Pressure (Psig)
°F
Psig
°F
Psig
63
178.5
79
231.6
64
181.6
80
235.3
65
184.3
81
239.0
66
187.7
82
242.7
67
190.9
83
246.5
68
194.1
84
250.3
69
197.3
85
254.1
70
200.6
86
258.0
71
203.9
87
262.0
72
207.2
88
266.0
73
210.6
89
270.0
74
214.0
90
274.1
75
217.4
91
278.2
76
220.9
92
282.3
77
224.4
93
286.5
78
228.0
PIPING PANEL
Page 32
°F
Psig
°F
Psig
94
290.8
110
365.0
95
295.1
111
370.0
96
299.4
112
375.1
97
303.8
113
380.2
98
308.2
114
385.4
99
312.7
115
390.7
100
317.2
116
396.0
101
321.8
117
401.3
102
326.4
118
406.7
103
331.0
119
412.2
104
335.7
120
417.7
105
340.5
121
423.2
106
345.3
122
428.8
107
350.1
123
434.5
108
355.0
124
440.2
109
360.0
The heat pump control (A175) provides the following
functions:
S
Demand defrost algorithm
S
Field−selectable defrost termination temperatures
S
Internal switching of outputs
S
Compressor anti−short−cycle delay.
S
Five−strikes lockout safety function
S
High (S4) and low (S87) pressure switches
S
Ambient (RT13), coil (RT21) and discharge line
(RT28) temperatures monitoring and protection.
COMPRESSOR PROTECTION
CYCLE DELAY
The heat pump control protects the compressor from:
S
Short cycling (five minutes) when there is initial power
up
S
Interruption in power to the unit
S
Pressure or sensor trips
S
Delay after Y1 demand is removed.
In non−communicating systems the delay is set for 300
seconds (five minutes) and can not be changed. To
override timer when active or inactive, place a jumper on
the field test pins between 1 and 2 seconds.
In communicating system, the icomfort Touch
has a separate built−in 5−minute non−adjustable short cycle
protection.
°F
Psig
°F
Psig
141
545.6
125
445.9
126
451.8
142
552.3
127
457.6
143
559.1
128
463.5
144
565.9
129
469.5
145
572.8
130
475.6
146
579.8
131
481.6
147
586.8
132
487.8
148
593.8
133
494.0
149
601.0
134
500.2
150
608.1
135
506.5
151
615.4
136
512.9
152
622.7
137
519.3
153
630.1
138
525.8
154
637.5
139
532.4
155
645.0
140
539.0
ANTI−SHORT
®
thermostat

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xp21−024Xp21−036Xp21−048Xp21−060

Table of Contents