When Connected to an Indoor Unit and an ventilator(ERV) together
(1) U sing One Wired Remote Controller to control multiple indoor units and ventilator(ERV)
Outdoor Unit
COM1(F1, F 2)
Indoor Unit
Wired Remote
Controller
(2) U sing One Wired Remote Controller to control indoor units connected to different outdoor unit and
ventilator(ERV)
Outdoor Unit
COM1(F1, F 2)
Indoor Unit
Outdoor Unit
COM1(F1, F 2)
Indoor Unit
• R egardless of the indoor unit's group address (RMC address), only the indoor units and ventilator(ERV) connected
to COM2 are controlled in group.
• W hen controlling indoor units and ventilator(ERV) together in group, you can control maximum of 16 indoor units
and ventilator(ERV).
• I f you want to use the power saving function, you have to connect Wired Remote Controller to only one indoor
unit and one ventilator(ERV).
• T he power cable (V1, V2) is not connected between indoor units.
• T he power cable for your Wired Remote Controller (V1, V2) should be connected to only one indoor unit.
COM1(F1, F 2)
Indoor Unit
COM2(F3, F 4)
COM2(F3, F 4)
COM2(F3, F 4)
COM2(F3, F4)
Ventilator(ERV)
COM1(F1, F 2)
Indoor Unit
COM2(F3, F 4)
Wired Remote
Controller
Ventilator(ERV)
COM2(F3, F 4)