Typical System Flow Rates - Viessmann VITODENS 200-W Technical Data Manual

Gas-fired wall-mounted condensing boiler 12 to 285 mbh (3.5 to 83.5 kw) multi-boiler installation 480 to 2280 mbh for models 45, 60 and 80
Table of Contents

Advertisement

Vitodens 200-W, B2HA 19 to 80 Technical Data

Typical System Flow Rates

Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HA 19
Output (NG/LPG)
t for NG/LPG
20º F rise
25º F rise
30º F rise
35º F rise
40º F rise
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HA 28
Output (NG/LPG)
t for NG/LPG
20º F rise
25º F rise
30º F rise
35º F rise
40º F rise
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HA 35
Output (NG/LPG)
t for NG/LPG
20º F rise
25º F rise
30º F rise
35º F rise
40º F rise
MBH
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
MBH
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
MBH
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
GPM (L/h)
1 boiler
61
6.1 (1385)
4.9 (1113)
4.0 (909)
3.5 (795)
3.1 (704)
1 boiler
91.2
9.1 (2100)
7.3 (1700)
6.1 (1400)
5.2 (1200)
4.6 (1000)
1 boiler
114
11.4 (2589)
9.1 (2067)
7.6 (1726)
6.5 (1476)
5.7 (1295)
System Flow Rates
11
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents