Boiler Control

Design and Function

Functions
Weather-compensated control of the boiler water
and/or flow temperature
Control of one heating circuit without mixer and two
heating circuits with mixer
Control of one heating circuit without mixer and two
heating circuits with mixer
Demand-dependent heating circuit pump and burner
off control
Adjustment of a variable heating limit
Anti-seizing pump protection
Integral diagnostic system
Maintenance display
DHW temperature control with priority
Control of solar DHW heating and central heating
backup in conjunction with the solar control module,
type SM1
Display of the solar energy yield
Auxiliary function for DHW heating (short-term
heating to a higher temperature)
Screed drying program
0-10V External signal input
Control Characteristics
PI characteristics with modulating output.
Time Switch
Digital time switch.
Individual and 7-day program
Automatic daylight savings time changeover
Automatic function for DHW heating and DHW
recirculation pump
Time, day and standard switching times for space
heating, DHW heating and the DHW circulation pump
are factory-set
Switching times are individually programmable,
i.e. up to four switching periods per day
Shortest switching interval: 10 minutes
Power backup: 14 days.
28
Vitodens 200-W, B2HA 19 to 80 Technical Data
Setting the Operating Programs
The heating system frost protection (see
frost protection function) applies to all heating programs.
You can select the following heating programs with the
program keys:
Heating and DHW
DHW only
Standby mode
External heating program changeover.
Frost protection
The frost protection function will be started when the
outside temperature drops below approx. 34° F (1° C).
With the frost protection function, the heating circuit
pump will be switched ON and the boiler water is
maintained at a lower temperature of approx. 68° F
(20° C).
The DHW tank will be heated to approx. 68° F (20° C).
The frost protection function will be stopped when the
outside temperature rises above approx. 37° F (3° C)
(default settings).
Summer Operation
Heating program "w"
The burner is only activated upon a call for domestic hot
water from the DHW storage tank (controlled by DHW
tank temperature sensor).