Waterside Flow

Waterside Flow (primary circuit)
The Vitodens 200-W, B2HB is designed for closed loop,
forced circulation hot water heating systems only. Use
standard friction loss method for pipe sizing. Observe
boiler maximum and minimum flow rate limitations. If
system flow rate exceeds boiler maximum flow rate
(as stated above), falls below the minimum flow rate
or if system flow rate is unknown, Viessmann strongly
recommends the installation of a low-loss header.
An alternative method may be used, such as primary
secondary piping using closely spaced tees.

Typical System Flow Rates

Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HB 19
Output (NG/LPG)
t for NG/LPG
20ºF (11ºC) rise
25ºF (14ºC) rise
30ºF (17ºC) rise
35ºF (19.5ºC) rise
40ºF (22ºC) rise
Boiler maximum flow rate 6.2 GPM (1400 L/h)
Model B2HB 26
Output (NG/LPG)
t for NG/LPG
20ºF (11ºC) rise
25ºF (14ºC) rise
30ºF (17ºC) rise
35ºF (19.5ºC) rise
40ºF (22ºC) rise
8
Flow rate
MBH
GPM (L/h)
6.4 (1453)
GPM (L/h)
5.1 (1163)
GPM (L/h)
4.3 (969)
GPM (L/h)
3.7 (830)
GPM (L/h)
3.2 (727)
MBH
GPM (L/h)
8.8 (1999)
GPM (L/h)
7.0 (1599)
GPM (L/h)
5.9 (1332)
GPM (L/h)
5.0 (1142)
GPM (L/h)
4.4 (999)
Vitodens 200-W, B2HB 19 to 35 Technical Data
A low-loss header offers additional benefits not provided
by a pair of closely spaced tees. Viessmann therefore
strongly recommends and prefers the use of a low-loss
header over closely spaced tees. See pages 25 and 26
for low-loss header information. Once the low-loss header
is connected, the built-in low-loss header logic of the
Vitodens 200-W boiler ensures the required
system through the sensory communication between the
low-loss header and the boiler.
Pressure drop (primary circuit) for
Vitodens 200-W, B2HB 19, 26, 35
For sizing an on-site circulation system.
Max. flow rate: 6.2 GPM (1400 L/h)
Boiler maximum flow rate 6.2 GPM (1400 L/h)
1 boiler
Model B2HB 35
Output (NG/LPG)
64
t for NG/LPG
20ºF (11ºC) rise
25ºF (14ºC) rise
30ºF (17ºC) rise
35ºF (19.5ºC) rise
40ºF (22ºC) rise
1 boiler
88
t across the
1 boiler
MBH
GPM (L/h)
11.7 (2657)
GPM (L/h)
9.4 (2126)
GPM (L/h)
7.8 (1771)
GPM (L/h)
6.7 (1518)
GPM (L/h)
5.9 (1328)
117