Heating Circuit / Boiler Pumps - Viessmann VITODENS 200-W Technical Data Manual

Gas-fired wall-mounted condensing boiler 12 to 285 mbh (3.5 to 83.5 kw) multi-boiler installation 480 to 2280 mbh for models 45, 60 and 80
Table of Contents

Advertisement

Vitodens 200-W, B2HA 19 to 80 Technical Data

Heating Circuit / Boiler Pumps

Viessmann offers a variety of Grundfos heating circuit/
boiler pumps which meet typical Vitodens system
installation requirements (see "Heating circuit pump
(field supplied)" or "Boiler pump (field supplied)" in the
Installation Examples starting on page 35). See tables
below for recommended pumps. Refer to the graphs on
page 10 and 11 for the proper waterside boiler friction
loss calculations. The following pumps have been selected
based on boiler heat exchanger head loss and boiler piping
to a low-loss header.
Model
Flow rate
20º F t
GPM (L/h)
25º F t
GPM (L/h)
30º F t
GPM (L/h)
35º F t
GPM (L/h)
40º F t
GPM (L/h)
GPM (L/h)
Flow limitation
Recommended boiler pumps
Model B2HA 45
14.6 (3316)
20º F t
11.7 (2653)
25º F t
9.7 (2211)
30º F t
8.3 (1805)
35º F t
7.3 (1658)
40º F t
Flow limitation
Model B2HA 60
20º F t
15.4 (3500)
25º F t
12.9 (2937)
30º F t
11.1 (2518)
35º F t
40º F t
Flow limitation
Model B2HA 80
20º F t
20.8 (4724)
25º F t
17.3 (3937)
30º F t
35º F t
40º F t
Flow limitation
B2HA 19
6.1 (1385)
4.9 (1113)
4.0 (909)
3.5 (795)
3.1 (704)
4.4 (1200)
Grundfos UPS 15-58 (3-speed), Taco 0015, Wilo Star S 21 FX
Flow rate
Boiler pressure drop
GPM (L/h)
15.8 (4.8)
10.0 (3.1)
7.5 (2.3)
5.8 (1.8)
4.2 (1.3)
Flow rate
Boiler pressure drop
GPM (L/h)
--
16.7 (5.1)
12.6 (3.8)
9.2 (2.8)
9.7 (2203)
7.5 (2.3)
Flow rate
Boiler pressure drop
GPM (L/h)
--
9.2 (2.8)
6.5 (2.0)
15 (3374)
4.8 (1.5)
13 (2953)
3.4 (1.0)
Before using the following pumps for a DHW tank
application, find out the proper pressure drop through the
tank, the required temperature difference through the coil
and system piping head loss of the domestic hot water.
IMPORTANT
Pump selection must be based on accurate system flow
and pressure drop calculations (includes DHW sizing).
B2HA 28
--
--
6.1 (1381)
5.2 (1184)
4.6(1035)
6.2 (1400)
Recommended
ft. (m)
pump option 1
UPS 26-99FC, 115V, Speed3
UPS 26-99FC, 115V, Speed2
UPS 26-99FC, 115V, Speed2
UPS 26-99FC, 115V, Speed1
UPS 26-99FC, 115V, Speed1
15.4 GPM (3500 L/h)
Recommended
ft. (m)
pump option 1
--
UPS 26-99FC, 115V, Speed3
UPS 26-99FC, 115V, Speed3
UPS 26-99FC, 115V, Speed2
UPS 26-99FC, 115V, Speed2
15.4 GPM (3500 L/h)
ft. (m)
--
25 GPM (5700 L/h)
Pump Information
B2HA 35
6.5 (1476)
5.7 (1295)
6.2 (1400)
Grundfos
UP 26-64F, 115V
Grundfos
--
UP 26-64F, 115V
UP 26-64F, 115V
Recommended pump Grundfos
--
UPS 26-99FC, 115V, Speed3
UPS 26-99FC, 115V, Speed2
UPS 26-99FC, 115V, Speed2
UPS 26-99FC, 115V, Speed2
--
--
--
Recommended
pump option 2
Grundfos
--
--
--
--
Recommended
pump option 2
Grundfos
--
--
--
13