Vitodens 200-W, B2HA 19 to 80 Technical Data

System Layout 6

Vitodens 200-W, B2HA with...
- DHW storage tank
- one heating circuit without a mixing valve
- two heating circuits with a mixing valve
- low-loss header
Legend
A
Vitodens 200-W B2HA boiler with
Vitotronic 200, HO1B outdoor reset control
B
Outdoor temperature sensor !
C
Vitotrol remote (optional)
Under floor heating circuit
D
E
Heating circuit pump
Mixing valve temperature sensor ?
F
Accessory kit for heating circuit with mixing valve
G
H
Heating circuit pumps
DHW storage tank
I
J
DHW tank temperature sensor %
K
Expansion tank
Temperature and pressure relief valve
L
M
Low-loss header
Viessmann temperature sensor for low-loss header %
N
Pressure relief valve
O
P
DHW recirculation pump
Radiator heating circuit
Q
Boiler pump
R
20
S
DHW circulating pump sA
*
Function based on coding of address 33
*
28/20
*
28/20
Installation of different heating circuits...
two heating circuits with 3-way mixing valve
(low-temp. circuit)
DHW production
... with the following flow conditions:
The total flow rate of the two heating circuits is greater
than the maximum possible water flow rate of the
Vitodens 200-W B2HA boiler (see page 10 for maximum
water flow rate of boiler).
The use of a low-loss header is strongly recommended.
The low-loss header is available as accessory part.
The 3-way mixing valve, built-in to achieve the low-
temperature level of the under floor heating circuit, is
controlled by an accessory kit for a heating circuit with
a mixing valve.
IMPORTANT
DHW circulating pump S must pump into the Vitodens
200-W B2HA boiler (as illustrated).
Installation Examples
45